10 kV配电架空线路综合治理工作的探析
2021-07-15王东林
王东林
摘 要:为有效应对城区配电架空线路设备本体运行状况差,部分县域地区雷击故障频发,线路运行环境复杂等因素造成配电架空线路故障多发情况,供电公司组织开展配电架空线路综合治理工作,落实开展配网架空线路治理专项行动,强化状态检测技术应用深入开展配网故障分析等各项工作措施,注重过程管控,确保治理质量,优化工作流程,提高治理水平,最终达到有效提升架空线路设备运行健康水平,降低配网故障的目的。
关键词:综合治理 配电网 运维 压降
中图分类号:TM751 文献标识码:A文章编号:1672-3791(2021)03(c)-0046-03
Analysis on Comprehensive Treatment of 10 kV Overhead Distibution Lines
WAN Donglin
(State Grid Changchun Power Supply Company, Changchun, Jilin Province, 130000 China)
Abstract: In order to effectively deal with the poor operation of urban distribution overhead line equipment, frequent lightning strikes in some county areas, complex line operation environment and other factors, the power supply company organized to carry out the comprehensive management of distribution overhead line, implemented the special action of distribution overhead line management, strengthened the application of state detection technology, and carried out in-depth management carry out the work measures such as distribution network fault analysis, pay attention to process control, ensure the quality of governance, optimize the workflow, improve the governance level, and finally achieve the purpose of effectively improving he health level of overhead line equipment operation and reducing the distribution network fault.
Key Words: Comprehensive management; Distribution network; Operation and maintenance; Voltage drop
1 城市配网架空线路运行分析及提升目标
1.1 配网架空线路问题分析
一是城市配电架空线路设备受历史因素影响,整体设备运行年限较久,设备老旧情况较为严重,故障频发;部分县域在雨季期间,雷击故障多发;配电架空线路绝缘化率整体较低,除市区架空线路基本实现绝缘化外,远郊区县配电架空线路裸导线占比较大,在大风、降雪等恶劣天气下,极易发生搭挂异物、树碰线等原因造成配网故障。二是设备本体故障占比较高,设备本体缺陷隐患引发故障较多。避雷器、绝缘子等设备本体故障发生率较高,该类设备运行年限较长,常规巡视手段发现缺陷困难,需加大力度彻底消除该类设备隐患。
1.2 提升目标
建立配网综合治理常态机制,充分发挥配电线路计划停电作用,连续每年完成80条故障率较高的配电线路的治理工作,实现配网整体故障率下降20%以上目标。……