APP下载

GIS组合电器设备受潮故障分析

2021-01-22杨海东,李传金,唐东升

今日自动化 2021年12期
关键词:分析研究

杨海东,李传金,唐东升

[摘    要]  在GIS变电站的设备端子箱以及机构箱部位,最常见的故障现象就是设备受潮,并且随着使用年限的增加,受潮程度将会更加严重。文章结合以往运行检修方案,针对设备的材料、设计与安装工艺、结构等方面展开研究,将为后期工作良好开展奠定基础。

[关键词]GIS;电器设备;受潮;分析研究

[中图分类号]T458 [文献标志码]A [文章编号]2095–6487(2021)12–0–02

Analysis of Moisture Failure of GIS Combined Electrical Equipment

Yang Hai-dong,Li Chuan-jin,Tang Dong-sheng

[Abstract]In the equipment terminal box and mechanism box of GIS substation, the most common failure phenomenon is that the equipment is damp, and as the service life increases, the degree of dampness will become more serious. Based on this, the article combines the previous operation and maintenance schemes, conducts research on the material, design and installation process, structure of the equipment, analyzes the common GIS equipment damp conditions, and then proposes relevant countermeasures for the later stage. The work is well developed and the foundation is laid.

[Keywords]GIS; electrical equipment; damp; analysis and research

在变电站中,GIS设备因其安装方便且维护工作量少、结构紧凑等优点,得到了广泛的认可与应用。GIS设备大部分是安装于户外环境的,由于露天的雨雪、露水等出现的潮气,无法进行有效的控制。在检修过程中,发现此环境中的设备受潮现象最为严重。当GIS设备受潮后:一方面会使设备内部的零部件出现锈蚀的现象,进而出现运行卡涩;另一方面还会使设备的绝缘性能下降,直接出现直流接地的现象。严重时将直接影响设备的正常运行。因此,在日常工作中,应该针对此方面展开充分的重视,将其中出现的问题进行积极的研究与探讨,以期能够采取有效的措施加以应对,提升设备的运行质量。

1 GIS设备受潮原因分析

变电站中GIS组合设备中容易出现受潮现象的是隔离开关机构箱、断路器机构箱、避雷器放电计数器连接盒、电流互感器端子箱,而引起受潮现象的主要有以下几内容:①结构设计以及制造工艺不合格,导致使用中密封不严密。②设备的密封条材质不合格,无法实现密封。③安装过程中工艺不合格和后期维护工作不及時,或者是加热器长时间未运行。……