Abstract: The volume of the rainwater and waste water pump room collection tank should be set reasonably according to the calculated water volume of rainwater and waste water to avoid setting it too large, at the same time, the pump flow rate should be selected reasonably according to the pump characteristics and start-stop requirements. In order to ensure the quality of the project and the reliability of operation, a water-raising pipe setting plan is given priority, and the management of each professional interface in the interval is strengthened.
Keywords: urban rail transit;section drainage;water pump selection;wastewater tank depth;water-raising pipe
某市城市軌道交通一期工程线路长度约为32 km,其中,地下区间线路长度约为23 km,高架区间线路长度约为8 km,剩余过渡段长度约为0.9 km。全线共设17座车站,其中,地下车站有14座,高架车站有3座,车辆基地设置为一段一场,地下车站穿越市内两条河流。
1 区间废水泵房设计
为了便于排水及节能,区间线路均为“高站位、低区间”的V字形,废水系统的区间废水泵房设置在区间线路实际坡度最低点,一般与区间联络通道合建在一起,废水泵房位于联络通道的下方,目前,绝大部分地铁线路采用这种形式,内设两台排水泵,一用一备,交替启动,必要时2台同时工作。
1.1 区间最大小时排水量的计算
1.1.1 区间隧道结构渗漏水。根据《地铁设计规范》(GB 50157—2013)相关条款要求,区间隧道结构渗漏水的平均渗漏量不应大于0.05 L/(m2·d),任意100 m2防水面积渗漏量不应大于0.15 L/(m2·d)。取渗漏量[q]为0.15 L/(100 m2·d),广东某线盾构区间直径[D]为6 m,对于不设中间风井的区间,距离一般不超过1.5 km,为便于计算,取长度[L]为1.5 km,则区间隧道结构设计渗漏水量[Qs]=[πD]×2L×[q]/100=84.78 L/d。
1.1.2 区间隧道消防废水。按照相关规范,全线消防按同一时间发生一次火灾考虑,车站发生火灾时,消防废水汇入车站废水泵房,区间发生火灾时,消防废水汇入区间废水泵房。……