某110kV变电站主变差动保护动作的原因分析
2021-11-28吴晨媛陆文钦
吴晨媛 陆文钦


摘要:针对某110 kV变电站主变开关跳闸事件,本文分析判断该开关两侧及上级相关保护动作行为的合理性,给出了故障原因,并成功消缺,最后提出防范及改进措施。
关键词:变电站;短路;主变差动保护
中图分类号:TM77 文献标识码:A 文章编号:1003-5168(2021)27-0086-03
Abstract: In view of a 110 kV substation main transformer switch tripping event,this paper analyzes the relevant protection actions on both sides of the switch and the upper level, and judges its rationality. On this basis, an analysis of the cause of the failure is given and the defect is successfully eliminated, and finally preventive and improvement measures are put forward to avoid the recurrence of similar incidents.
Keywords: substation; short circuit; main transformer differential protection
1 事故概況
事故发生前,某变电站711开关(110 kV侧某出线开关)、700开关(1号主变110 kV侧开关)为运行状态,712开关(110 kV侧某出线开关)为热备用状态,10 kV母线分列运行。站内主变差动保护装置型号为南瑞继保RCS-9671B。
10月23日14:36分,1号主变差动速断、比率差动保护动作跳711、700及101开关(1号主变10 kV侧开关),110 kV备自投经延时动作合712开关(正确动作),因该站10 kV侧没有自投装置,所以10 kV母线失压[1],而后监控合10 kV母线分段100开关,恢复送电。
随即,运行及检修人员赶到现场对有关一、二次设备进行检查。现场对1号主变差动保护装置查看发现,装置内部的事件记录如表1所示。由以往工作经验可知:
①变压器保护根据容量大小有所不同。大型电力变压器的主保护有机变大差动、差动、瓦斯、速断等,后备保护有过负荷等,还有油温高报警等。可见差动是变压器的主保护之一。
②变压器差动保护是专用于变压器的差动保护,一般为速断,也可以根据要求设置延时或报警,而差动速断保护不仅用于变压器,也可以用于电缆两端以及其他用电设备的差动保护上。
③一般情况下,比率制动原理的差动保护能作为电力变压器主保护,但是在严重内部故障时,短路电流很大的情况下,严重饱和使交流暂态传变严重恶化,它的二次侧基波电流为零,高次谐波分量增大,反应二次谐波的判据误将比率制动原理的差动保护闭锁,无法反映区内短路故障。……