关于规范低压开关防跳二次回路设计的分析思考
2021-11-28陆文钦吴晨媛
陆文钦 吴晨媛


摘 要:所谓跳跃是指由于合闸回路手合或遥合接点粘连等原因,造成合闸输出端一直带有合闸电压的现象。当开关因故障跳开后,会立刻合上;而保护动作开关会再次跳开,因为一直加有合闸电压,开关又会再次合上。上述情况被通俗地稱为“开关跳跃”。一旦发生开关跳跃,开关会被损坏,所以防跳功能是操作回路中一个必不可少的部分。
关键词:低压开关;防跳回路;接线设计
中图分类号:TM77 文献标识码:A 文章编号:1003-5168(2021)27-0034-03
Abstract: The so-called jump refers to the phenomenon that the closing circuit hand-closed or remote joining joint bonding and other reasons, resulting in the gate output has been with the closing voltage. When the switch jumps off due to a fault, it will close immediately, and the protective action switch will jump off again, because the closing voltage is always applied, and the switch will close again. The above situation is popularly known as "switch jump" .Once the switch jumps, the switch will be damaged, so the anti-jump function is an essential part of the operating circuit.
Keywords: low voltage switch; anti-jump circuit; wiring design
近年来,变电站低压开关二次控制回路已逐步开始应用开关自带的防跳回路[1-2]。大部分厂家,特别是合资厂家配备的防跳回路为电压启动、电压保持型防跳回路,而有些厂家的防跳回路存在一些设计缺陷,从而导致开关分闸后无法再合闸[3]。防跳是典型的一、二次专业交界面内容,也是现场工作常见的“盲区”。近年来,发生了多起因防跳回路不完善导致保护动作不正确故障,引起了相关专业的重视,出台了众多条例。公众号后台有人在问这个问题,今天就给大家梳理一下。防跳是“防止开关跳跃”的简称,所谓“跳跃”是指当断路器手动或自动合闸在有故障的线路上,继电保护装置将动作跳闸。此时,如果操作人员仍将控制开关放在合闸位置,或自动重合闸装置的触点未复归,断路器将发生再次合闸。因为线路上故障未消除,保护装置又动作于跳闸,从而出现多次“跳合”现象。其后果是,造成断路器的遮断能力下降或损坏,甚至引起爆炸事故。……