气象自动站雷击事故分析及防护对策

2018-07-09王银

海峡科技与产业 2018年1期

摘要:气象观测设施都处在空旷的高地,每年因雷击造成气象设施损坏事件时有发生,特别是处在雷电多发区的广东省,近年来集成化程度高、耐压水平低的气象自动站的普遍应用,因雷击造成气象设施损坏的事件呈增长趋势。文章就多年来广东省气象自动站发生的雷击事故调查、统计及分析,从防直击雷、防闪电感应、地电位反击以及等电位连接等方面分析其雷击事故原因,找出防雷系统存在的缺陷,提出相应的防御对策。

关键词:气象自动站;雷击事故;防护对策

中图分类号:P415.12 文献标识码:A

Abstract: Meteorological observation stations are located in open heights. Damage to meteorological observation equipment caused by lightning strikes occurs from time to time every year. Especially in Guangdong Province, where lightning is concentrated. in recent years, the use of integrated meteorological automatic stations with low pressure resistance is common.Based on the lightning accidents occurring at Guangdong meteorological automatic station for many years, the causes of lightning strike are analyzed from the aspects of direct lightning strike, lightning protection induction, lightning protection, surge invasion and equipotential connection. The defects of lightning protection system are found out, and corresponding countermeasures are put forward.

Key words: Meteorological automatic station;lightning accident;Protective countermeasures

氣象自动站的数据采集和传送主要通过高密度的集成电路采集器来完成。广东省有相当一部分气象台站使用的是无锡公司,特别是华云公司生产的DZZ5,主采集器型号为HY3000,其采集器电子元件的耐压水平低,对周围电磁环境的变化反应敏感。文中从气象自动站工作原理、雷击事故等五个方面进行分析,提出整改措施。

1 气象自动站工作原理

气象自动站由数据采集器、传感器、通讯模块、交直流电源等组成。数据采集器采用HY3000系列单板机,组成原理见图1。

自动站采用交直流两路电源供电。220V市电供电正常时,稳压电源输出电压为直流13.8~14.5V,由内部DC/DC转换成+5V、±12V电压供系统和传感器工作。停电时由蓄电池直接输入直流14V电压。观测设施各类传感器采集的信号通过屏蔽信号线传输至数据采集器,由数据采集器进行处理后经RS232串口传输至计算机。

220V市电电源、稳压电源输入端内置有电涌保护器,数据采集器的信号输入端口均设有内置防雷单元,接地线分别接至金属外壳共用接地点,通过PE线引入接地装置。……