2018-01-31毛焱汤晓晖

科技创新与应用 2018年4期
关键词:变电站

毛焱 汤晓晖

摘 要:继保二次设备定检是确保变电站继电保护装置安全可靠运行的重要途径,而定检过程中的二次措施执行则有效保障了定检工作本身的安全性,其中,退压板部分对整个定检工作显得尤为重要。文章针对二次措施中投退压板部分进行优化分析,设计了一种压板状态比对工具,有效保障了定检后压板的正确状况,确保了定检工作顺利完成。

关键词:二次措施单;变电站;继电保护装置

中图分类号:TM76 文献标志码:A 文章编号:2095-2945(2018)04-0015-02

Abstract: Secondary equipment inspection is an important way to ensure the safe and reliable operation of substation relay protection devices, and the implementation of secondary measures in the determination and inspection process effectively ensures the safety of the determination and inspection work itself. It is very important for the whole checking work in the part of the depressurized plate. In this paper, according to the optimization analysis of the secondary measures, a pressure plate state comparison tool is designed, which effectively guarantees the correct condition of the pressure plate after its fixed inspection, and ensures the smooth completion of the determination and inspection work.

Keywords: secondary measure list; substation; relay protection device

1 设计压板状态比对工具的重要性

随着变电站设备的不断增加,站端继电保护二次设备定检工作任务也逐渐加重。为了保障定检工作的安全、顺利开展,南方电网颁布了继电保护二次回路工作安全技术措施单管理要求。面对当前繁杂的二次措施纸质记录,能有效执行二次措施显得尤为重要。针对在定检过程中需多次发生变化的压板措施,文章设计了一种有效的压板状态比对工具,在确保二次措施安全可靠执行的前提下,大大提高了工作效率。

2 二次措施单格式及填写规范

二次措施单是确保工作票所列安全措施以外的二次设备及回路工作安全技术措施规范、有效地落实的书面记录。南方电网近期制定了最新二次措施管理要求,其中总体要求是指在保护、安自装置及其二次回路或相关一次设备工作时,工作负责人或其指定的工作班成员应根据工作内容、工作地点、一次设备停电范围、二次设备运行状态、二次回路设计等实际因素,充分评估工作过程对相关联二次设备或回路的影响,必要时应制定二次安全措施。……