基于DSP的井下低压供电系统选择性漏电保护的研究
2016-06-16朱敏薛峰
朱敏+薛峰



摘要:漏电在井下环境中产生的危害大,影响范围广,因此要求漏电保护装置可靠、速动及有选择性。该文提出的总馈电开关处采用附加直流电源检测,分支开关处采用零序电流幅值和零序功率方向的融合选线方式,双重选线方式防止误判错判,总开关和分开关都采用DSP(TMS320F28335)为控制器,总分复用,提高漏电保护的可靠性、灵敏性及准确性。
关键词:井下低压供电;漏电保护;选择性;DSP
中图分类号:U223 文献标识码:A 文章编号:1009-3044(2016)10-0280-03
Abstract: The mine environment on the low voltage power grid is bad, therefore the leakage protection is put forward the requirements of reliability, quick acting and selectivity. The main switch and branch switch of this system all chooses DSP (TMS320F28335) as the controller. The total controller and the branches processor use the method of total score reuse, which means that if the total controller has something wrong, we can by selecting a branch controller as the general controller to avoid the total controller problem which caused by accidents. This method can avoid the failure of the leakage effectively. Through the design of hardware circuit and software programming method, this system can judge the leakage fault and choice the leakage branch correctly.
Key words: underground low-voltage power grid ; electric leakage protection ; selectivity; DSP
漏电是井下低压供电系统所面临的重要安全隐患,极大影响井下正常生产,因此漏电保护装置起着至关重要的作用。当前市场中的漏电保护装置不够灵敏,易出现误动拒动等现象,本文提出的基于DSP(TMS320F28335)控制器的总分复用形式,在总馈电开关处采用附加直流电源检测法检测漏电电流,在分支模块处采用零序电流和零序功率法进行融合选线,在处理器的使用上在总馈电开关处和分支馈电开关处都采用本控制器,当系统中的总控制器出现状况,其他分支处理器能够在第一时间替代总控制器,有效避免因为装置控制器的故障导致的漏电现在,提高了系统的可靠性。
1原理方法
1)附加直流源
电网发生漏电故障的主要表现特征之一就是对地绝缘电阻的下降,附加直流电源检测主要是通过直流电源,向系统中注入直流,这个直流就可以实现低压电网绝缘水平的连续检测。这里我们可以通过直流继电器和千欧表显示的直流电流值来对绝缘电阻的大小进行判断。……