广蓄A厂技术供水泵跳闸分析及处理
2014-04-21罗盛杨
【摘要】: 介绍了广蓄A厂机组技术系统的组成及正常运行方式,介绍了广蓄A厂#1/#2机组侧技术供水系统#1泵跳闸事件的处理过程,结合二次图纸对故障原因进行了详细分析,有助于对以后发生类似故障时的处理提供参考。
【关键词】:抽水蓄能;技术供水泵;跳闸;分析;处理
中图分类号:TV674文献标识码: A
Analysis and Treatment of The Technical Water Supply Pump Tripping in Plant A of Guangzhou Pumped Storage Power Station
Luo Sheng Yang
(Guangzhou Pumped Storage Power Station,Conghua cityGuangdong province510950)
Abstract: The paper introduces the normal operation mode of the unit technical water supply pump of plant A in Guangzhou pumped storage power station,and introduces the process of the technical water supply pump tripping treatment, carries out a detailed analysis of the causes of the failure by combined with secondary drawings, and will contribute to the processing of the occurrence of similar failures in future.
Key words: pumped storage ; technical water supply; tripping ;analysis;treatment
0引言
广州蓄能水电厂位于广州从化境内,分为A、B厂两期建成,共安装8台单机容量为300 MW的可逆式水泵水轮电动发电机组,总装机容量2400 MW。电站设计水头为535 m,机组额定转速为500 r/min。广蓄电厂主要承担广东电网调峰、填谷、调频及事故备用任务,其机组具有发电、抽水、调相等多种工况运行且工况转换频繁等特点。所以,作为机组重要辅助设备的技术供水系统,对机组起着极其重要的润滑冷却作用,当机组无冷却水运行时,会直接导致机组跳机。
1广蓄A厂机组技术供水系统简介
1.1机组技术供水系统的组成
广蓄A厂机组技术供水系统由#1/#2机组侧技术供水系统11SRG、#3/#4机组侧技术供水系统12SRG两个单元组成。其中11SRG单元供#1机组、#2机组冷却用水,为01SRG、02SRG单机供水回路提供水源。12SRG单元供#3机组、#4机组冷却用水,为03SRG、04SRG单机供水回路提供水源。两个单元独立运行,通过直径为DN450的联络管连接,必要时可打开中间联络阀 20SRG 036VE互为备用。每个单元由三套水泵---电动机---自动过滤器组成。其中二套主用,一套备用。机组技术供水的用户为:电动发电机空气冷却,上、下导轴承冷却器,水泵水轮机推力轴承,水导轴承,调速系统集油箱冷却器,上、下迷宫环及水导油槽外腔。……