APP下载

利用邻机同期装置电压采样优化发电机假同期试验方案

2021-01-12郑子暄郑宇

今日自动化 2021年11期

郑子暄 郑宇

[摘    要]发电机假同期试验是检验发电机同期装置及其回路正确及完整性的有效手段。常规的假同期试验准备工作繁杂,需进行腾空高压母线等操作,因而具有高耗时性,发电机空载持续长时间运行造成能源的极大浪费。利用邻机同期装置电压采样优化发电机假同期试验方案,既保障了机组安全性又兼顾了机组经济性。

[关键词]假同期;同期装置;电压采样;试验

[中图分类号]TM31 [文献标志码]A [文章编号]2095–6487(2021)11–00–02

Optimization of Generator False Synchronization Test Scheme by Voltage

Sampling of Adjacent Generator Synchronization Device

Zheng Zi-xuan, Zheng Yu

[Abstract]Generator false synchronization test is an effective means to check the correctness and integrity of generator synchronization device and its circuit. The preparation of the conventional false synchronization test is complicated, and the high-voltage bus needs to be vacated, so it is time-consuming. The generator runs without load for a long time, resulting in a great waste of energy. The generator false synchronization test scheme is optimized by using the voltage sampling of adjacent generator synchronization device, which not only ensures the safety of the unit, but also takes into account the economy of the unit.

[Keywords]false synchronization; synchronizing device;voltage sampling;test

若發生发电机非同期并网事件,极易发生设备损坏事故造成电网的扰动。因此,机组检修后或发电机同期回路检修后,为确保同期回路的正确性与完整性,都需进行假同期试验。对于发电机假同期试验的方法有很多,本文通过2×350 MW机组及220 kV双母输电系统入手分析假同期试验的方法,为同类机组或相似机组的假同期试验方法的优化进一步说明,此优化方法大大节约了时间,缩短了机组空载运行时间,提高了经济效益。

1 假同期试验的常规方法

假同期试验是用一种模拟的方法进行假的并列操作,试验时将发电机并网断路器的隔离开关断开,但将其辅助触点短接。发电机空载升压后,启动同期装置,同期装置判定电压、频率、相角符合要求后,发并列指令,发变组出口开关合闸。若同期回路的接线有误,则不能完成上述工作。通过上述方法,校验同期装置接线及装置本身的功能正确性。

2 系统架构及常规方法应用

假同期试……