基于PI系统对公用介质综合能耗的研究和应用
2021-01-12吴海龙
吴海龙
[摘 要]随着工业化的发展,使用公用介质越来越普遍,企业为了做大做强,想方设法减少成本,不断开展节能降耗工作。文章利用PI系统对循环冷却水、5 ℃冷冻水、7 ℃冷冻水、压缩空气四种介质进行运行数据收集、整理和分析,对公用介质综合能耗实现在线监控,找出公用介质系统最佳的运行模式,帮助企业减少运行成本。
[关键词]节能降耗;PI系统;公用介质;综合能耗
[中图分类号]TU201.5 [文献标志码]A [文章编号]2095–6487(2021)11–00–02
Research and Application of Comprehensive Energy
Consumption of Public Media Based on PI System
Wu Hai-long
[Abstract]With the development of industrialization, the use of public media has become more and more common. In order to become bigger and stronger, enterprises have tried every means to reduce costs and continue to carry out energy-saving and consumption-reducing work. The article uses the PI system to collect, organize and analyze operating data for four media: circulating cooling water, 5 ℃ chilled water, 7 ℃ chilled water, and compressed air, and realize online monitoring of the comprehensive energy consumption of public media, and find out the best public media system The operating mode helps companies reduce operating costs.
[Keywords]energy saving and consumption reduction; PI system; public media; comprehensive energy consumption; optimal
1 概述
本文研究对象为珠海某公司的公用介质生产工艺。该公司耗电量大的公用介质生产工艺主要包含循环冷却水系统、5 ℃冷冻水系统、7 ℃冷冻水系统、压缩空气系统(以下四大系统统称为公用介质)。其中,循环冷却水系统出水量约8 000 m3/h,一半提供给5 ℃冷冻水系统、7 ℃冷冻水系统、压缩空气系统当作冷却介质使用,一半提供给其他生产系统使用。5 ℃冷冻水系统用于其他生产系统;7 ℃冷冻水系统用于空调和其他生产系统;压缩空气系统提供给仪表装置和其他生产系统,各介质均要求稳定。
2 公用介质单位耗电的评价方法