一起变压器重瓦斯动作事故分析
2020-08-25张洪东刘瑞胡庆男王琛
张洪东 刘瑞 胡庆男 王琛



摘 要:本文主要对一例220 kV变压器气体继电器重瓦斯动作故障原因进行分析,首先,通过变压器油色谱分析、直流电阻、变比测试、绝缘电阻及介损试验等分析手段,排除主变本体自身故障,然后初步断定为变压器波纹储油柜故障,最后提出具体的故障处理对策。希望本文的分析和处理方法可为现场处理类似故障提供参考。
关键词:变压器;气体继电器;储油柜;卡涩
中图分类号:TM407文献标识码:A文章编号:1003-5168(2020)19-0036-04
Abstract: This paper mainly analyzed the cause of a 220 kV transformer gas relay heavy gas action fault. Firstly, through the analysis methods of transformer oil chromatogram analysis, DC resistance, transformation ratio test, insulation resistance and dielectric loss test, the main transformer body fault was eliminated, and then the fault was preliminarily determined as the transformer corrugated oil conservator fault. Finally, the specific fault treatment countermeasures were proposed. It is hoped that the analysis and treatment method in this paper can provide reference for similar fault treatment on site.
Keywords: transformer;gas relay;oil conservator;jamming
随着国民经济的飞速发展,社会对电力负荷的需求越来越高,进一步推动了变电站的建设。电力变压器是发、输、变、配电系统中的重要设备之一,其性能、质量直接关系到电力系统运行的可靠性和运营效益。为了保证电力变压器安全稳定运行,防止事故扩大,应为之配置一系列的保护措施,如差动保护、瓦斯保护等。其中,瓦斯保护动作主要反映变压器的内部故障。当变压器油箱内部存在短路或接地等故障时,高温电弧使絕缘油产生大量气体,油气混合物迅速向上涌入瓦斯继电器,进而推动瓦斯挡板动作,从而接通跳闸回路。而由非电量引起的瓦斯保护动作的例子相对较少,以下是一起由外油式储油柜运行过程中滚轮卡涩造成重瓦斯动作的案例。
1 故障概述
某变电站2#主变(电压等级220 kV),型号为 SFSZ11-240000/220,2020年2月13日,主变压力释放阀动作,2.6 s后重瓦斯保护动作跳闸,三侧开关跳闸,所有负荷均备投成功。表1为故障发生时具体的动作保护时序表。……