探析10kV配电线路雷击事故产生原因及防雷措施
2020-08-16李娉婷
李娉婷
摘 要:10kV配电网的安全稳定运行,常因雷击事故发生,给供电的稳定性与安全性带来不利影响,也严重影响生产与生活的正常用电。通过对10kV配电线路常见雷害事故产生原因进行分析与总结,才能为科学采取相应防雷措施提供技术支持。更好的保障配电线路运行安全,为人们生产、生活提供良好的用电服务。
关键词:10kV配电线路;雷击事故;原因;防雷措施
中图分类号:TM863 文献标志码:A 文章编号:2095-2945(2020)23-0139-02
Abstract: The safe and stable operation of 10kV distribution network is often caused by lightning accidents, which not only adversely affects the stability and safety of power supply, but also seriously affects the normal power consumption of production and life. By analyzing and summarizing the causes of common lightning accidents in 10kV distribution lines, we can provide technical support for scientifically taking corresponding lightning protection measures. It can better ensure the safe operation of distribution lines and provide good electricity services for people's production and life.
Keywords: 10kV distribution line; lightning accident; cause; lightning protection measures
在供電工作中,10kV配电线路的安全稳定运行,与社会生产和人民生活用电关系密切,因此,电力工作者需要确保10kV配电线路处于良好运行,这也是各级供电部门的工作重点。在实际工作中,10kV配电网的安全稳定运行,常因雷击事故的发生,给供电的稳定性与安全性带来不利影响,也严重影响生产与生活的正常用电。为此,需要重视对10kV配电线路发生雷击事故的原因进行认真分析与总结,才能及时发现配电网运行过程中发生的雷击隐患,及时采取相应的安全措施,防止雷击事故发生,更好的保障配电线路的运行安全,为人们生产、生活提供良好的用电服务[1]。
1 雷击事故产生的成因、主要形式及危害
雷击导致的过电压一般称为大气过电压,它是指在电力系统,电力相关的线路、设备及建筑等受到大自然雷击或雷电感应后而产生的。雷击产生的过电压幅值很大,对于10kV配电系统而言,其过电压幅值可高达300~400kV,这样高幅值的冲击电压不仅可以将变压器直接烧毁。……