变电所直流电源柜接地故障的分析及处理

2020-06-21智春香王智垚

河南科技 2020年11期

智春香 王智垚

摘 要:高压开关柜是变电所的主要供电设备,而直流电源柜输出直流电,给高压开关柜的操作系统提供電源。本文介绍了直流电源柜接地的分类和原因,阐述了查找直流电源柜接地故障点的常用方法和技巧,并结合实例,分析如何快速做好接地故障处理,确保直流电源柜设备良好运行。

关键词:直流电源柜;接地故障点;检测方法

Abstract: The high-voltage switchgear is the main power supply equipment of the substation, and the DC power cabinet outputs DC power to provide power to the operating system of the high-voltage switchgear. This paper introduced the classification and causes of the DC power cabinet grounding, explained the common methods and techniques for finding the ground fault point of the DC power cabinet, and combined with examples to analyze how to deal with the ground fault quickly to ensure the good operation of DC power cabinet equipment.

Keywords: DC power supply cabinet;ground fault point;detection method

变电所直流电源柜由蓄电池组、充电设备及微机显示装置组成,输出直流电,通过敷设控制电缆至变电所内每个高压开关柜的二次系统,给变电所主要供电设备高压开关柜的操作系统提供电源[1]。高压开关柜的操作系统包含二次控制、保护、信号系统和自动综合保护装置等。在变电所供电系统停电的情况下,它可以保证高压开关柜的控制回路、信号回路、保护装置正常工作,正确显示设备故障发生时产生的现象,便于快速进行事故处理。因此,直流电源柜的安全稳定运行对保证变电所供电系统安全有着非常重要的作用。

1 直流电源柜接地的分类及原因

1.1 直流系统电源柜接地的类型

直流电源柜的输出为直流电源,分为正极和负极,作为带极性的电源设备,其接地故障按电源的极性可分为正极接地和负极接地;按接地的种类,可分为直接接地和间接接地;按接地的接触情况,可分为单点接地、多点接地和绝缘接地[2]。

1.2 直流电源柜接地的原因

1.2.1 设计原因。受专业知识储备的局限,人们可能对设备性能了解不深,对控制和保护装置内部原理理解不透彻,电气设计与相关专业的协调不够细致,会造成交、直流回路的接线混乱。……