一起低压配电越级跳闸事例分析
2020-03-13张伟明
张伟明


摘 要:越级跳闸在电力系统特别是低压配电系统中,因为保护级配偏差、管理偏差等问题时有发生,发生越级跳闸事件会使故障进一步扩大,给日常安全生产带来巨大威胁。文章以一起干式变压器跳闸事件为例,详细的分析了故障原因、检查方法以及后续的对策和管理提升手段,可为日常运维管理提供借鉴。
关键词:干式变压器;照明;越级;跳闸
中图分类号:TM862 文献标志码:A 文章编号:2095-2945(2020)08-0071-03
Abstract: In the power system, especially in the low-voltage distribution system, the over-stage trip occurs from time to time because of the protection gradation deviation, management deviation and other problems, which will further expand the fault and bring a great threat to the daily production safety. Taking a dry-type transformer tripping event as an example, this paper analyzes the fault causes, inspection methods and follow-up countermeasures and management promotion measures in detail, which can provide reference for daily operation and maintenance management.
Keywords: dry-type transformer; lighting; overstep; tripping
引言
越级跳闸是指在电力系统发生故障时,应由保护整定优先跳闸的断路器来切除故障,但因各种原因优先跳闸断路器未跳闸,由其它断路器跳闸来切断故障,造成失电范围变广,这种称为越级跳闸。发生越级跳闸事件会使故障进一步扩大,给日常安全生产带来巨大威胁。在低压配电系统中,因为保护配置偏差、断路器性能偏差以及日常管理偏差等问题容易发生越级跳闸事件。
1 设备基本情况
厂用电压选择采用6kV一级电压,采用动力中心(PC)和电动机控制中心(MCC)的供电方式。6kV开关柜采用中置式真空气开关柜或F+C回路柜,对于额定功率小于1000kW的电动机和1250kVA以下的变压器,供电主回路采用接触器加熔断器的方案;等于或大于1000kW的电动机和等于或大于1250kVA的变压器,供电主回路采用真空斷路器。低压厂用变压器的低压绕组中性点均采用直接接地,低压变压器选用环氧树脂浇注干式变压器,变压器电压比为6.3±2×2.5%/0.4kV,接线组别为D,yn11。380V厂用电系统保护利用低压空气开关自身的保护或熔断器保护。……