APP下载

基于布尔对OUPA的数学建模及优化

2018-04-04张翼洲梁义郜参观俞月娇

现代电子技术 2018年7期

张翼洲 梁义 郜参观 俞月娇

摘 要: 基于在低压电力系统中的OUPA只有物理实体,没有数学模型的前提下,首次提出使用布尔代数对其进行描述,从数学建模的角度补充了OUPA在理論上的空白;在建立数学模型之后,对其模型进行优化,主要解决目前长期存在于低压线路中由功率因数变化引起继电器误动的问题,以逻辑门电路为基础,高速微低功耗处理器为核心重新设计新一代OUPA模型,为三相线路下智能互联OUPA的同步控制奠定理论基础。

关键词: 低压线路; OUPA; 布尔代数; 功率因数; 逻辑电路; 继电器; 建模

中图分类号: TN911.1?34 文献标识码: A 文章编号: 1004?373X(2018)07?0130?05

Boolean?based mathematical modeling and optimization of OUPA

ZHANG Yizhou, LIANG Yi, GAO Canguan, YU Yuejiao

(College of Electronic and Information Engineering, Yili Normal University, Yining 835000, China)

Abstract: In the condition that the OUPA (over voltage and under voltage protective device with auto?reclosing function) in low?voltage power system only has the physical entities, and hasn′t the mathematical model, the Boolean algebra is first used to describe the OUPA, which can fill in its theory blank from the perspective of mathematics modeling. The mathematical model was established and optimized. Aiming at the relay misoperation in low voltage line generated by the variation of power factor, the logic gate circuit is deemed as the basis and the high?speed low?power consumption processor is taken as the kernel to redesign a new generation OUPA model, which lays the theoretical foundation for the synchronous control of intelligent interconnection OUPA in three?phase line.

Keywords: low?voltage line; OUPA; Boolean algebra; power factor; logic circuit; electric relay; modeling

0 引 言

自恢复式过欠压保护装置(Over Voltage and Under Voltage Protective Device with Auto?Reclosing Function,OUPA)是当供电线路出现过电压、欠电压时,保护器能在持续高压冲击下迅速、安全地切断电路,避免异常电压送入终端电器造成事故的发生,当电压恢复正常值,保护器将在规定时间内自动接通电路,确保终端电器在无人值守情况下正常运行,适用于单相交流电压为220 V,频率为50 Hz,额定工作电流为60 A及以下的用户或负载。作为由中性线故障引起的单相线路过、欠电压对单相用电设备的保护,主要用于家庭及商场配电(单相AC 230 V,三相四线AC 415 V)线路中作为过电压、欠电压、断相、断零线保护用。

在低压配电系统中,由于中心线断线、三相负载严重不平衡、错相等原因造成单相线路过电压、欠电压,导致单相用电设备烧毁与损坏[1]。因此,2012年4月开始实施的行业标准JGJ 242?2011《住宅建筑电气设计规范》6.3.2规定:“每套住宅应设置自恢复式过、欠电压保护电器。……

登录APP查看全文