66kV相控电抗器烧毁故障分析
2017-10-10李绘妍赵明淑汤思涵王禹霏
李绘妍,赵明淑,魏 晔,汤思涵,王禹霏
(国网抚顺供电公司,辽宁 抚顺 113008)
66kV相控电抗器烧毁故障分析
李绘妍,赵明淑,魏 晔,汤思涵,王禹霏
(国网抚顺供电公司,辽宁 抚顺 113008)
简述了干式空芯电抗器的结构原理和用途,以及干式空芯电抗器在运行中常见的几种故障。详细介绍了李石寨变电站66 kV SVC用相控干式空芯电抗器烧毁事故的经过,对干式空芯电抗器烧毁事故的原因进行了论证、分析,找到设计、制造过程中,由于线圈的绝缘存在质量问题,覆膜绝缘制造工艺存在先天缺陷,导致匝间短路,致使大面积烧毁。提出了为避免此类事故再次发生,应该加强出厂及交接感应耐压试验。
电抗器;漏磁;局部过热;匝间击穿;污闪
Abstract:This paper describes the dry air core reactor structural principle and purpose, while briefly dry air core reactors in operation several common faults. It says in detail the substation 66 kV SVC with phased-dry type air core reactor burn accidents through .The dry type air core reason reactors burn accidents are demonstrated, analysis and using the popular elimination.Finally it finds the design, manufacture process.Due to quality problems insulated coil, the inter-turn short circuit, resulting in a large area burned. To avoid such accident happen again, we should strengthen the factory and handover induced overvoltage with stand test.
Keywords:reactor;leakage flux;local overheating;breakdown;pollution flashover
电抗器又称电感线圈(L),在电力系统中被广泛应用,是能在电路中起阻抗(XL)作用的电气设备。电力系统中采用的电抗器,按其绕组内有无铁芯分为铁芯式电抗器和空心式电抗器2种形式,油浸铁芯式电抗器的结构与变压器相似,主要由线圈、铁芯和油箱等部件组成,干式空芯式电抗器实质上就是一个无导磁材料的空芯线圈[1]。
干式空芯电抗器的绕组,是用聚脂薄膜绝缘的铝导线绕成的多个单层线圈,其首尾端是分别并联的。层间用聚脂薄膜或间隔放入空气气道作为绝缘或散热,实际上相邻间接近同电位,故层间绝缘较可靠[2]。绕组绕成后干燥浸渍聚脂并固化,在其上下放置类似蜘蛛网状防磁材料支架夹紧,支架下用绝缘子和撑脚固定于地面基础,基础混凝土的各钢筋间需相互绝缘,不能构成回路,以防止漏磁引起涡流损耗[3]。……