低气压环境下开缝翅片管换热器换热性能研究
2017-01-12张慧晨柳建华徐小进张良戚大威
张慧晨+柳建华+徐小进+张良+戚大威



摘 要: 利用低气压环境模拟装置对开缝翅片管换热器在不同气压下的换热性能进行实验研究.研究结果表明:随着气压不断降低,换热器周围空气密度逐渐降低,换热器空气侧换热系数以及显热换热量逐渐降低,而空气含湿量随着气压降低逐渐升高,导致潜热换热量逐渐增加;当气压降至0.058 MPa以下时,换热器空气侧潜热换热量占主要部分,当气压为0.04 MPa时,换热器换热能力与常压下相比下降了36.63%.
关键词: 低气压; 开缝翅片管换热器; 换热性能; 实验研究
中图分类号: TK 172文献标志码: A
文章编号: 1008-8857(2016)03-0181-05
Abstract: Heat transfer performance on the air side of split fin tube heat exchanger under different air pressures were tested by using the low pressure environment simulation device.Results showed that heat transfer coefficient and the sensible heat would diminish along with the air density under low pressure.Meanwhile,the Moisture content was increased,which would make the latent heat increased accordingly.And the latent heat would exceed the sensible heat when the air pressure was lower than 0.058 MPa.The heat exchange performance would drop 36.63% compared to the normal pressure when the air pressure was decreased to 0.04 MPa.
Keywords: low pressure; split fin and tube heat exchanger; heat transfer performance; experimental study
翅片管换热器由于制造简单、结构紧凑、适用范围广而广泛应用于制冷与空调设备中[1].而地区环境不同,换热器的工作能力随之发生变化.例如,从上海至拉萨的青藏铁路客车空调的实际运行过程中所经历的地区环境较为复杂,平均海拔相差4 km,对应的气压相差约26.8 kPa,因此,客车空调器的换热能力也会受到相应的影响.而在距地表20~30 km的平流层内,由于有着其他大气层环境所没有的稳定气象条件和良好电磁特性而定点悬浮了大量的飞行器[2-4].在平流层内,气压低至4 kPa,空气密度约是常温常压下空气密度的1/20,因此,换热器空气侧换热效率将大幅降低.而翅片管换热器的主要热阻集中在空气侧[5],因此空气侧换热能力是影响换热器换热效率的关键.
目前,对翅片管换热器的研究工作主要集中在常压下换热器结构、翅片结构、来流空气状态等对换热器换热效率的影响.例如,李妩等[6]对我国空调行业几种常用的翅片管换热器换热性能进行实验研究,并得出雷诺数、翅片间距以及管排数对换热器空气侧换热性能影响的计算关联式;……