浅析三门核电厂设备冷却水系统运行失效和处理措施
2016-11-03王文武
王文武
【摘 要】三门核电是全球首座三代核电技术AP1000核电厂,与传统成熟的压水堆核电厂技术最大不同是安全系统使用了“非能动”技术。设备冷却水系统(CCS)虽然不是安全相关,但作为纵深防御系统能够在事故情况下协助“非能动系统”更快更好地缓解和终止事故。在正常运行和停堆换料期间,CCS运行也是保证电厂发电或余热导出的关键环节。所以核电厂操纵员必须熟练掌握CCS系统运行,包括失效现象及处理措施,保证电厂安全运行。
【关键词】CCS;失效现象;处理措施
Analyses of Sanmen Nuclear Plant Component Cooling System Operation Failures and Solutions
WANG Wen-wu
(Sanmen Nuclear Power Company Ltd., Sanmen Zhejiang 317112, China)
【Abstract】Sanmen nuclear power is the worlds first third generation nuclear power technology AP1000 nuclear power plant. Compared with traditional pressurized water nuclear power plant, the biggest difference of Sanmen nuclear power is“passive”technology used in safe systems. Although Component Cooling Water System(CCS)is not safe related, it is a defense system in depth to assist the passive systems faster and better in mitigation and termination of the accident. In the normal operation and during refueling time, CCS operation also is a key to ensure the power generation and decay heat out of the reactor. So nuclear power plant operators must be familiar with the CCS system operation, including the failure phenomenon and solutions to ensure the safe operation of the power plant.
【Key words】CCS; Failure phenomena; Solution
0 引言
众所周知,核电厂产生的热量中只有一部分用于发电,大部分热量被各种冷却水带走,例如电厂正常功率运行期间乏汽的热量在凝气器中被海水带走,停堆冷却第二阶段一回路冷却剂的热量通过余热排出热交换器(简称RNS)被设备冷却水系统(简称CCS)带走。
1 系统功能
三门核电厂CCS系统主要是带走电厂衰变热和各种负荷设备产生的热量,将热量传递给最终热阱——大海(三门核电正常运行和停堆的最终热阱为大海,事故期间最终热阱为大气)。按照设计,CCS系统可实现安全功能,纵深防御功能和非安全相关功能。
1.1 安全功能
CCS系统三个安全壳电动隔离阀在收到安注信号(S信号)或主泵轴承水温度高2信号后会自动关闭,从而隔离CCS安全壳管线,防止安全壳内放射性物质释放到环境中。
1.2 纵深防御功能
电站正常冷却期间向RNS供应冷却水,避免失去RNS余热排出能力而触发电站非能动热交换器(简称PRHR);……