AbstractTaking the distribution network in an industrial park as an example, the reactive power loss is calculated and the reactive measurement problem is analyzed. Then according to the problems existing in user-side distribution network, measures and suggestions to avoid the reactive power evaluation are expounded.
Keywordsreactive power loss, charging power, metering, no-load
0引言
在电力系统中,存在两种功率:有功功率和无功功率。有功功率是用来维持负载正常工作的电功率,可转换为其他形式的能量;无功功率则是用来维持设备电磁场的正常建立,在电网中的波动会占用发电机等无功电源的出力,还会引起电压波动,改变网络损耗。因此,供电企业对用户从电网吸收的无功电能会进行计量和奖惩考核。
由于用电侧的配电网结构、负荷类型、网络运行方式等对无功电能的计量有很大影响,所以,用电侧无功损耗的计算和分析对于规划、设计和运行阶段的合理性都有着较为重要的指导意义。
1实例分析
图1为某工业园区内的配电网结构,地区110/10kV变电站内主变2台,110kV侧为双母线接线、10kV侧为单母线分段接线,从10kV侧两段母线分别引出2路电源线(556出线、560出线、555出线和559出线)为10kV开闭所的四段母线供电。每一路电源线均设2条型号为YJV22-3X185(8.7/15kV)的电缆,单条电缆长度约为500m。10kV开闭所运行方式为两组(四段)母线,均分段运行,出线侧带有本建筑内10台型号为SCB11~10/0.4kV的干式变压器及一座相距约600m的变配电室(内设2台型号为SCB11-10/1000的变压器)。开闭所(AH28和AH35出线)引至该变配电室的两路电源线为YJV22-3X240(8.7/15kV)。在地区110/10kV变电站10kV出线侧、10kV开闭所进、出线侧均装有智能计量表。
表1为该园区内10kV配电网IV段查抄到的多级计量数据,以110/10kV变电站10kV侧计量点数据作为收费依据,由表1可以看出该点连续几个月功率因数都在0.3左右,远低于标准要求的0.9。

表1 某园区10kV配电网IV段多级计量数据
1.1变压器无功损耗……p>
猜你喜欢
杂志排行
智能建筑电气技术的其它文章
- Application of Navigation System Based on iBeacon Technology in Tourist Attractions
- Design and Application of Security and Protection System of Residential Park Project
- Optimization of Power Distribution System of Fire Fighting Equipment
- Electrical Design of Electric Vehicle Charging Facilities for Civil Building
- Promoting the Use of LED Lighting from the Design Stage
- Case Analysis of Electric Vehicle Charging Facilities in Residential District