(国网四川省电力公司电力科学研究院,四川 成都610072)

摘要:35 kV低压配电系统中性点一般采用不接地方式,当低压母线发生单相短路,在故障消失后低压母线TV上会产生很高的过电压,造成铁心严重饱和, 近而产生很高的过电流,此电流极有可能导致TV熔丝熔断;针对此问题推导了单相故障消失后TV过电流的物理机制并提出相应的抑制措施,最后通过PSCAD/EMTDC软件搭建了一个实际电力系统模型,验证了此物理机制并证明了抑制措施的可行性。

关键词:单相接地故障;TV熔断;中性点不接地系统;PSCAD

Abstract:35 kV distribution network is usually an isolated neutral system, when encountered an single-phase earth fault and after the fault disappears, a high voltage will be produced on TV of low-voltage bus which makes the core saturated seriously, and then a high current will occur, so the TV fuse has a extremely high risk to be fused. Aiming at the problem, the physical mechanism of TV vercurrent after a single-phase earth fault disappears is deduced and the corresponding suppression measures are proposed. At last, the PSCAD/EMTDC software is used to establish a real power system model to test the physical mechanism, and it proves the feasibility of the proposed suppression measures.

Key words:single-phase earth fault; TV fuse; isolated neutral system; PSCAD

0引言

2014年的5月26日、5月30日以及7月1日,四川攀枝花的110 kV白岩子变电站35 kV母线TV别发生了A相、C相以及B相熔丝熔断的情况。配电系统TV丝熔断不仅会影响电费的计量,造成很大的损失,严重时甚至烧毁TV[1]。另外,高压熔断器本身的熔断也是一种损失,更换也比较麻烦。还有,当TV一次侧高压熔断器熔断时,可引起系统虚假接地,开口三角电压升高,引起继电器误动作,容易造成工作人员的误判,将其当成系统接地,而花费很多时间还找不到接地点。这些情况对于电力系统安全、稳定、可靠的运行都是十分不利的。因此,为保证电力系统的正常运行,电磁式TV压熔断器熔断[2-3]的研究就显得非常重要[4]。

在10 kV、35 kV中性点不接地配电网[5]中,母线上安装的电磁式TV常采用的是Y0/Y0的接线方式;……