某市大型居住小区负荷增长特性研究
2016-06-07胡春华程淑英
胡春华,程淑英,王 宇
(国网内江供电公司,四川 内江 641000)
某市大型居住小区负荷增长特性研究
胡春华,程淑英,王宇
(国网内江供电公司,四川 内江641000)
摘要:从OPEN3000调控系统中提取专线用户负荷数据,对某地级市多个大型居住小区多年用电负荷进行了统计;分析其最大负荷率、长时负荷水平、增长特性,进而与原供电方案中计算负荷的比例关系进行了对比分析;分析计算负荷测算和变压器的选取是否适当,以期对电网规划、供电方案编制起到决策参考作用。
关键词:配电网;计算负荷;居住小区;变压器;规划
Abstract:The load data of special power line are extracted from the OPEN3000 control system, and power loads for many years of several large residence communities in a prefecture-level city are collected for statistics. The maximum load factor, long-time load level and growth characteristics are analyzed and then its proportional relationship with the calculated load in the original power supply schemeis compared. Finally, whether the calculation of load and the selection of transformer are proper is analyzed, which may play a role in decision making for power grid planning and power supply scheme programming.
Key words:distribution network; calculated load; residential district; transformer; planning
引言
目前,供电公司对大型居住小区用电负荷增长特性未有效开展跟踪分析。实际工作中,涉及到配电网规划、大型居住小区供电方案制定时,往往以经验来测算负荷、选择参数,缺乏实证检验。
文献[1]规定居住建筑用电30~70 W/m2(4~16 kW/户)、公共建筑用电40~150 W/m2、工业建筑用电40~120 W/m2、仓储物流建筑15~50 W/m2、市政设施建筑20~50 W/m2。文献[2]规定配电变压器的长期工作负载率不宜大于85%。文献[3]规定一般客户的计算负荷宜等于变压器额定容量的70%~75%;建筑面积在50 m2及以下住宅用电每户容量宜不小于4 kW;大于50 m2的住宅用电每户容量宜不小于8 kW。
某供电公司在供电方案中测算小区负荷时一般根据每套建筑面积大小50 m2、90 m2、144 m2以下,分别取4 kW、6 kW、8 kW,同时系数取0.3~0.4;商业按60 W/m2、车库及设备房按10 W/m2测算,同时系数取0.7;小区道路按装机计算,同时系数取0.7;消防、电梯等负荷按最大用电需量进行测算。这样算出总计算负荷后,再根据每栋建筑的计算负荷,按照单元选择标准变压器;……