基于Dig SILENT的风电场并网暂态稳定分析与比较
2016-06-07杜旭浩马天祥魏力强孙翠英
杜旭浩,马天祥,魏力强,孙翠英
(国网河北省电力公司电力科学研究院,河北 石家庄 050021)
基于Dig SILENT的风电场并网暂态稳定分析与比较
杜旭浩,马天祥,魏力强,孙翠英
(国网河北省电力公司电力科学研究院,河北 石家庄050021)
摘要:随着大型风电场的不断投入,其并网暂态稳定问题,也受到人们的关注。基于Dig SILENT仿真平台,分别建立了含有双馈和永磁同步直驱两种不同风力发电机组的电网仿真计算模型。结合某风电场的接入实例,模拟了A市电网发生N-1三相短路故障时,两种不同风力发电机组的暂态稳定情况,并对仿真结果进行了分析比较,给出了参考建议。
关键词:风电场并网;暂态稳定;N-1;双馈;永磁直驱
Abstract:With the continuous integration of large-scale wind farms with the grid, the transient stability problem caused by grid connection is attracted more and more attention. Based on Dig SILENT, the simulation model of power grid is established containing two kinds of different wind power generation units, that is, double-fed and permanent magnet direct drive. According to an integration example of a wind farm, the transient stability of these two kinds of wind power generation units is simulated during N-1 three-phase short-circuit fault. The simulation results are analyzed and compared, and the reference suggestions are given.
Key words:grid-connected wind farm; transient stability;N-1; double-fed; permanent magnet direct drive
0引言
随着风电技术的不断研究和发展,中国风电产业逐渐走向规模化,然而大型风电场接入电网会对系统的安全稳定运行带来影响,尤其是系统的暂态稳定问题[1]。当系统发生大扰动时,大容量的风电场应尽量避免简单的切机措施,采取提高故障穿越能力等措施,为系统的暂态稳定提供支撑[2]。
为了考察电网发生大扰动期间,风电场保持并网运行的能力,基于Dig SILENT仿真平台,建立了含有风电场的电网仿真计算模型。模拟了A市电网发生N-1三相短路故障时,风电场并网公共连接点PCC点的母线电压以及有功、无功出力的变化情况,并对风电场采用双馈和永磁同步直驱两种不同风力发电机组并入电网时的情况,进行了分析比较,给出了恰当的建议,对今后的风电场入网暂态稳定研究及其他同类型机组的通流试验研究有一定实际意义。……