隔离开关发热原因分析及预防措施探讨
2012-06-04张斌斌
张斌斌
【摘要】变电设备的隔离开关容易发生发热缺陷,影响电网的安全运行,导致社会效益和经济效益的损失,本文通过分析统计某500kV变电站隔离开关发热的原因,结合变电站运行人员专业的实际,介绍了正确处理发热缺陷的方法,提出了预防设备发热的措施,规范巡视和测温,以确保设备安全可靠地运行。
【关键词】发热;发热原因;处理方法;预防措施
【 abstract 】 the substation equipment isolating switch prone to fever defects, influence the safety operation of the power grid, leading to social benefit and economic benefit of loss, this paper through the analysis of 500 kV substation isolating switch a fever, the reasons of the substation operation personnel with professional practice, introduces the method of correctly handle fever defects, and puts forward the measures of prevention equipment fever, regulating the patrol and temperature measuring, to ensure that equipment safe and reliable operation.
【 key words 】 fever; Fever reasons; Processing methods; Prevention measures
中图分类号:TM643文献标识码:A文章编号:
引言
近几年,由于供电负荷迅速增长,加之部分设备未及时进行改造更换或维护不力,致使变电站隔离开关发热现象时有发生,严重影响供电的可靠性和电网的安全运行。据统计,在2008—2009年期间,某500kV变电站因隔离开关发热达到重大紧急缺陷级别而需要立即采取措施处理的次数达十六起,所以采取预防措施及时发现设备发热缺陷并对其进行正确的处理,可以避免该缺陷蔓延扩大,避免非计划性停电,确保电网的安全运行。
1隔离开关发热原因分析
1.1隔离开关发热图片及相对温差值计算
按公式1计算出相对温差值,按表2的规定判断设备缺陷的性质。
式中:τ1和T1——发热点的温升和温度;
τ2和T2——正常相对应点的温升和温度;
T0——环境参照体的温度。
计算:相对温差值%=(T1-T2)/(T1-T0)*100%=(111-35.9)/(111-35)*100%=0.988≥95
视同紧急缺陷
1.2隔离开关发热原因分析
1.2.1隔离开关本身质量问题。部分老隔离开关,在检修调试确无问题的情况下,正常运行电流不超过额定值的60%,但仍会发热;隔离开关的转动支点因制造工艺不良引起发热。……