APP下载

对电力电缆故障检测的分析

2012-06-04刘晓生

城市建设理论研究 2012年13期
关键词:检测

刘晓生

中图分类号:TM247 文献标识码: A 文章编号:

摘要:当今城市10kV中压配电网中,电力电缆以其维护工作量少、稳定性高且有利于城市美化等优点,得到了广泛的应用,目前许多城市电网规划首选电力电缆。但因电缆线路大多较为隐蔽的特点,一旦发生电缆故障,故障点的查找将十分麻烦,如何快速、准确地判定故障性质和故障点位置,及时排除故障是供电部门经常面临的一个重要课题。本文重点介绍利用行波在长线路上传输的理论对电缆故障点进行预定位的几种方法以及这些方法在实际中的应用。

关键词:二(多)次脉冲法;电缆故障;检测;冲击电流法

Abstract: the current urban 10 kV in medium voltage distribution network, power cable with its maintenance, high stability, and less to beautify cities etc, and a wide range of applications, now many of the city grid plan preferred power cables. But for most cable line a more subtle features, once produce cable faults and fault point search would be very troublesome, how to quickly and accurately determine fault properties and fault points, and promptly eliminate the fault is the power supply departments often facing an important issue. This article introduced the traveling wave in the long term by way of transmission theory of cable fault point are a scheduled several methods of these methods and its application in practice.

Keywords: 2 (more) time pulse method; Cable faults; Detection; Impact current method

1电缆故障的分类

10kV电缆故障类型多样,此电压等级的电缆运行要求当然没有110kV的电缆高,其外护套有少许破损仍能安全运行,不能定性为故障。一般而言,10kV电缆故障多见于相间短路、单相短路接地以及多相短路并接地故障。若按故障点的特性阻抗来分,一般可分为低阻故障和高阻故障。低阻故障指故障点的直流电阻为零或不为零但小于电缆特性阻抗10倍的故障(一般认为小于200Ω),高阻故障为直流电阻大于电缆特性阻抗10倍以上的故障,但在实际检测工作中并不要求很严格地区分。

2电缆故障的原因

电力电缆发生故障的原因很多,主要有以下几种主要原因:

(1)机械损伤:包括安装时不小心造成的机械损伤或靠近电缆施工造成的机械损伤,有时如果损伤不严重,要几个月甚至几年才会导致损伤部位彻底击穿形成故障。……