小城市配电系统中性点接地分析
2012-06-04王为
王为
摘要:针对配电网覆盖的不断扩大及城市化进程中电缆馈线回路数的不断增加,系统中单相接地电容电流也在不断的增大。合理选择配电电网中性点的运行方式,已成为关系到电网运行可靠性的关键问题之一,文中就电网的中性点接地方式进行了分析,对各接地方式的相应特点进行了描述,并阐述了自己的观点。
关键词:配电系统;中性点;接地;分析
Abstract: Based on the constant expansion of distribution network covers and the increasing of cable feeder loop number in urbanization process, the capacitance current of single-phase grounding in system is also be constantly increased. Reasonably choosing the operation mode of distribution grid neutral has become one of the key points relating to the operation reliability of the power grid. This paper analyses the ways of the neutral point grounding in the power grid, describes the corresponding characteristics of each grounding method, and then expounds his own views.
Keywords: power distribution system; neutral point; grounding; analyse
中图分类号: TU852 文献标识码:A文章编号:
1.前言
我国电力系统中性点的运行方式主要分为:大电流接地系统和小电流接地系统。大电流接地系统是指中性点直接接地系统,在我国主要是指110kv以上系统和低压配电系统,在发生单相接地短路时,由于执着地电流较大而使断路器跳开起到保护作用。这样做,在低压系统可以对人身起到较好的保护作用,在110kv以上系统则可以节约大量的绝缘费用。我的的0.4kv低压配电系统属于中性点直接接地系统,低压配电系统按接地形式不同,分为:IT、TT、和TN系统,TN系统又具体分为TN-C、TN-S、TN-C-S系统。小电流接地系统是指中性点经抗接地或者不接地系统,在我国主要是指中压配电系统。在发生单相接地时,继电保护一般设定为不立即跳闸,而是可以持续运行两个小时。
中压配电网以6kv、10kv、35kv三个电压等级应用最为普遍,且均为小电流接地系统,随着供电网络的发展,架空线路和电缆线路的不断延伸,特别是采用电缆线路的用户日益增加,使得系统中单相接地电容电流不断增大,导致电网单相接地故障可能发展为事故。……