APP下载

国华九江电厂10kV公用段快切装置误动分析及处理

2020-03-08聂英丽

今日自动化 2020年9期

聂英丽

[摘    要]随着科学技术的进步,百万千瓦火电机组已成为目前主力机组,对于一个百万机组的发电厂而言,厂用及公用系统电源供电的连续可靠运行,是实现各种用电设备安全稳定运行,以确保机组可靠运行的基本条件,为了实现供电可靠性,重要场合配有双路电源供电,两路电源切换依靠快切装置、备自投、ATS等实现电源的可靠切换,而对于厂用及公用10 kV系统,一般配置厂用电切换装置,那么快切装置的稳定运行在机组运行中就发挥着至关重要的作用,如何避免快切装置误动,确保负荷的连续不断电运行的就发挥着重要意义。

[关键词]快切装置;可靠运行;不断电运行

[中图分类号]TM564 [文献标志码]A [文章编号]2095–6487(2020)09–00–02

[Abstract]With the progress of science and technology, one million thermal power units have become the main units at present. For a power plant with one million units, the continuous and reliable operation of power supply for auxiliary and public systems is the basic condition for realizing the safe and stable operation of various electrical equipment and ensuring the reliable operation of units. In order to realize the reliability of power supply, double power supply is provided in important occasions, The switching of two-way power supply relies on fast switching device, automatic switching device, ATS, etc. for auxiliary and public 10 kV system, the auxiliary power switching device is generally configured, so the stable operation of the fast switching device plays an important role in the unit operation. How to avoid the misoperation of the fast switching device and ensure the continuous and continuous power operation of the load plays an important role.

[Keywords]fast cutting device; reliable operation;continous power operation

本文主要针对国华九江电厂10 kV公用段快切装置误动进行原因分析,并且针对分析原因采取改进措施,通过长期运行观察,证明采用大功率继电器后,降低了长电缆引起的干扰问题,提高快切装置可靠性。

神华国华九江电厂一期工程以500 kV一级电压接入系统,厂内为3/2接线方式,通过二回500 kV线路(华石I线、华石II线)至石钟山变。高压厂用母线为单母线分段接线,每台机组设2段10 kV厂用母線,分别为10 kV A段和10 kV B段,由高厂变两个分裂绕组及启备变两个分裂绕组分别供电,主厂房辅机的公用、单元负荷及脱硫负荷分别接入10 kV A段和10 kVB段。10 kV A段和10 kV B段母线正常运行时,由各自高厂变供电,备用电源为启备变。正常运行时启备变断路器断开,当工作电源因故障断开时,由快切装置进行切换,由启备变带电,承担全部厂用负荷。……

登录APP查看全文