降低通信设备在蓄电池组放电过程中断风险研究
2019-09-10刘元泼
刘元泼




摘 要:“十三五”计划对智能电网提出了新的要求。随着智能电网的发展,电力通信的发展进入了全新阶段。通信电源是通信系统的“心脏”,必须保障通信电源安全有序运行,才能保证通信设备正常运行,进而保障电网的安全稳定。目前,电力通信设备使用的基本是-48V的直流电源系统,蓄电池作为通信直流系统的第二道屏障,其放电过程对通信设备的影响必须得予重视。
关键词:智能电网;通信设备;通信直流电源系统;蓄电池
中图分类号:TN929.5;TM912 文献标识码:A 文章编号:1003-5168(2019)23-0127-03
Research on Reducing the Risk of Interruption of
Communication Equipment in Battery Discharge Process
LIU Yuanpo
(Guangdong Power Grid Co., Ltd., Maoming Power Supply Bureau,Maoming Guangdong 525000)
Abstract: The 13th five-year plan makes new requirements for smart grid. With the development of smart grid, the development of power communication has entered a new stage. Communication power supply is the "heart" of communication system. It is necessary to ensure the safe and orderly operation of communication power supply, so as to ensure the normal operation of communication equipment and the safety and stability of the power grid. At present, the basic power communication equipment is a -48v dc power supply system. As the second barrier of the communication dc system, the battery's discharge process must be taken seriously.
Keywords: smart grid;communication equipment;communication dc power supply system;battery
1 電力通信设备直流电源系统
电力通信设备直流电源系统主要由高频开关电源、蓄电池组、直流配电和电源监控等设备组成,为通信设备提供-48V直流电源。在正常情况下,高频开关电源整流模块将输入的市电(交流电源)转化为直流后供电给通信设备,同时给蓄电池充电。当市电由于故障停电时,蓄电池组放电供给通信设备。南方电网通信电源技术规范规定:设于变电站、开关站的通信站蓄电池组放电时间不少于8h。
2 电力通信设备中断对电力生产业务的影响
目前,电力通信设备基本由-48V直流电源系统供电,蓄电池放电过程中,若全程压降使得通信设备输入电压低于设备保护电压,将会导致变电站内绝大部分通信设备发生中断,导致通过传输设备传输的继电保护和调度数据网等生产业务中断,严重情况下可导致电力2级事件。
3 电力通信设备在蓄电池放电过程中断的影响因素……p>