化工厂再沸器泄漏原因分析
2019-09-10崔岩王振明崔骞
崔岩 王振明 崔骞




















摘 要:某化工厂丁烯解析塔再沸器发生泄漏。为查明原因,防止类似事件再次发生,本文首先进行取样与检查,然后开展样品检测,分析其泄漏原因,最终提出预防措施。
关键词:化工厂;再沸器泄漏;丁烯解析塔;原因分析
中图分类号:TQ05 文献标识码:A 文章编号:1003-5168(2019)23-0117-04
Analysis of Leakage Causes of Reboiler in Chemical Plant
CUI Yan1 WANG Zhenming1 CUI Qian2
(1. Shandong Institute for Product Quality Inspection,Jinan Shandong 250100;2. Qingdao Economic and Technological Development Zone Haier Water Heater Co., Ltd.,Qingdao Shandong 266500)
Abstract: A chemical plant butene analysis tower reboiler leaked. In order to find out the reasons and prevent similar incidents from happening again, this paper first conducted sampling and inspection, then carried out sample testing, analyzed the causes of the leaks, and finally proposed preventive measures.
Keywords: chemical plant;reboiler leakage;butene analysis tower;cause analysis
某化工厂丁烯解析塔再沸器为立式管侧热虹吸再沸器,其优点为循环速度高,传热膜系数高于水平式,有很好的防垢作用,特别适用于高分子材料;其缺点是垂直管不易拆卸、清洗及维修,另外,塔底液面高度大约与再沸器上部管板处于同一水平面,这就提高了塔底的标高,使造价增大[1]。再沸器结构如图1所示,实物如图2所示。
发生泄漏的再沸器工作压力、工作温度、工作介质等信息如表1所示。
1 取样与检查
对再沸器进行拆解取样,如图3所示。上端管板与换热管连接处可见部分管子端口被焊接封堵,厂家人员介绍,泄露主要发生在某些换热管的管壁上以及换热管端头与管板的焊接处。发生泄露后,厂家已将涉及的管子全部进行了封堵。被封堵的换热管均在蒸汽进口附近,进一步拆解发现,蒸汽进口处的防冲挡板已经脱落,目视可见防冲挡板与筒壁焊接部位未熔合,如图4所示。
由于已经封堵的换热管已经破坏了其原始形态,故从临近的尚未发生泄漏的区域截取试样,样品照片如图5所示。封堵的管子上普遍发现存在漏点,如图6所示。沿未封堵的换热管轴向将换热管和管板切割开,结果发现,换热管和管板间有肉眼可见间隙,换热管平直、无明显变形,如图7所示。……