对两台电站锅炉主蒸汽管道安装监督检验发现问题的思考
2018-11-21斯锋
斯锋
【摘 要】电站锅炉范围内管道以前作为监管缺失环节,法规要求纳入锅炉管理体系以来,从事安装监督检验过程中,根据两台锅炉安装监督检验遇到的问题,从相关法规及安全技术规范条款缺少及模糊的,提出个人意见及措施。
【关键词】电站锅炉;主蒸汽管道;配管
中图分类号: TM621.23;TG115 文献标识码: A 文章编号: 2095-2457(2018)20-0236-002
DOI:10.19694/j.cnki.issn2095-2457.2018.20.108
【Abstract】pipelines within the scope of power station boilers used to be the missing part of supervision, and since the regulations were required to be incorporated into the boiler management system, personal opinions and measures have been put forward in the process of installation supervision and inspection according to the problems encountered in the supervision and inspection of two boilers according to the lack and ambiguity of relevant regulations and safety technical specifications.
【Key words】Power station boiler;Main steam pipeline;Piping
0 引言
电站锅炉范围内管道是指主给水管道、主蒸汽管道、再热蒸汽热段管道和再热蒸汽冷段管道[1]。随着TSG G0001-2012《锅炉安全技术监察规程》、TSG G7001-2015《锅炉监督检验规则》的实施,再次明确锅炉范围内管道的范围。自从四大管道纳入锅炉监管体系后,特别是在2016年当阳市马店矸石发电有限责任公司“8·11” 主蒸汽管道爆裂事故之后,作为一线检验人员发现在锅炉范围内管道安装监督检验中的风险把控难度大。因在安装检验过程中,发现相关标准规范中的条款,存在模糊、跟实际工作不相适应等情况。
1 概况
两台锅炉都是2016年新装,管道由电力设计院设计,设计院给出管材、管件、阀门、支吊架的材料清单、依据标准。序号1锅炉范围内管道是16年9月开工,主蒸汽管道为母管制,预留1台锅炉。序号2锅炉范围内管道是16年10月开工,管道为单元制。详见下表1:
两台锅炉的主蒸汽管道都存在相同管材质量问题,序号1的锅炉,管道安装由锅炉制造单位现场进行配管、安装,材料由业主自行采购。安装后对热处理后的焊口采用便携式里氏硬度计进行硬度检测时,发现焊口硬度偏高,普遍为190~200HB,安装单位查阅热处理记录和对焊口进行金相检测,未发现异常,再对现场管道母材进行硬度复查时,发现母材硬度普遍为170~180HB。……