关于风电场35kV母线PT柜综合接地保护装置优化探讨
2018-11-21王则会
王则会
摘 要:针对某风电场35kV风机集电线路电缆中间接头接地故障,引发35kV母线PT柜内相间短路,结合现场实际情况和故障录波波形全面分析接地故障产生的原因,认为是典型的接地故障。可以确认故障性质和范围,为查找故障点提供依据。对照防范措施要求,防止类似不安全事件重复发生并提出相应的处理办法及改进措施。
关键词:风电场;35kV母线PT柜;综合接地保护装置
中图分类号:TM614 文献标志码:A 文章编号:2095-2945(2018)28-0134-02
Abstract: In view of the grounding fault of the middle joint of the cable of the 35kV fan collecting line in a wind farm, the phase to phase short circuit in the PT cabinet of the 35kV bus bar is caused. Combined with the actual situation on the spot and the fault wave recording waveform, the causes of the grounding fault are comprehensively analyzed, and it is considered to be a typical grounding fault. It can confirm the nature and scope of the fault, and provide the basis for finding the fault point. According to the requirements of preventive measures, I need to prevent the recurrence of similar unsafe events and hereby put forward the corresponding treatment and improvement measures.
Keywords: wind farm, PT cabinet with 35kV bus bar, comprehensive earthing protection device
1 设备故障原因分析
某风电场由于风机集电线路电缆中间接头接地故障,产生间歇弧光过电压,在35kV母线PT柜内引发相间短路,导致智能型接地综合保护装置(以下简称ZN05A装置)在保护期间出现C相绝缘子击穿、高压限流熔管熔断、一次保护回路侧C相铜排烧断,35kV低压侧主变保护柜过流跳闸,导致引发系统失压。造成主变过流保护动作,主变高压侧(1101)、主变低压侧(3501)开关全部跳闸。
从故障录波图看出(见图1),事件起因是35kV系统1号集电线路A相接地,弧光放电,随后发生了长达十几秒21次间歇弧光过电压,最高相电压超过正常值3倍(70kV),持续过电压使35kV系统三相绝缘降低。
集电线路电缆中间接头发生单相非金属性接地,产生间歇弧光过电压,扩大原因:
(1)综合接地保护装置未及时动作和有效缓解单相接地故障。
35kV系统是不接地系统,接地保护原理是在接地相投入电抗器,抵消接地电容电流,起到消弧作用。查故障录波记录(见图1),A相发生弧光接地时,接地综合保护装置未及时动作;……