关于防雷接地中的冲击接地电阻分析
2018-09-21王红坡
王红坡
摘要:本文以人工垂直接地极为例,依据相关计算,对影响冲击接地电阻的相关因素进行模拟,并从中指出其与冲击接地电阻之间所存在的关系,以此来更加全面、深入、系统化的去认识冲击接地电阻。通过对比两个有效长度的计算公式,指出其在现实工作中所存在的基本出入,以此为更好的开展防雷检测及接地工作提供指导与帮助。
Abstract: In this paper, taking the artificial vertical grounding pole as an example, according to the relevant calculations, the relevant factors that affect the impact grounding resistance are simulated, and the relationship between it and the impact grounding resistance is pointed out, so as to know the impact grounding resistance more comprehensively, in-depth and systematically. By comparing the calculation formulas of two effective lengths, it is pointed out that there are fundamental differences in the actual work, so as to provide guidance and assistance for better carrying out lightning protection detection and grounding work.
關键词:接地;冲击接地电阻;防雷
Key words: grounding;impact grounding resistance;lightning protection
中图分类号:TM862 文献标识码:A 文章编号:1006-4311(2018)27-0146-03
0 引言
针对冲击接地电阻而言,其与工频接地电阻之间存在较大差异。现阶段,防雷检测部门通过检测建筑物防雷接地情况,从中所获得的数据都是工频接地电阻。据《建筑物防雷设计规范》得知,防雷建筑物类型不同,对其所要求的冲击接地电阻是存在差别的。现实操作中,防雷检测人员直接把检测所得工频接地电阻值作为冲击接地电阻值,并且还将其写入到具体的检测报告当中,这与规范要求不相符。即使利用换算系统将冲击接地电阻换算出来,因公式自身存在不足与缺陷,同样会出现误差。本文借助于人工垂直接地电阻的具体计算公式与其冲击系数,指出对冲击接地电阻造成影响的各种因素,且通过换算公式的对比,来更加深入的认识冲击接地电阻,为相关防雷接地工作提供参考与指导。
1 接地电阻的基本定义
1.1 工频接地电阻
传统架构下所定义的接地电阻,均为工频接地电阻;从根本上来讲,就是一定电流通过接地极流入到大地时,接地极与无穷远处的零电位面间的电流I与电位差V的比值。……