摘 要:匝间绝缘击穿是干式空心电抗器匝间绝缘故障的最终表现形式,过电压下的局部放电是引起匝间绝缘损伤的主要因素之一。为研究干式空心电抗器匝间绝缘局部放电随电压变化的发展规律,在局部放电屏蔽室内搭建了试验平台。参照35kV干式空心电抗器匝间绝缘的工艺制造要求,制作了匝间绝缘局部放电试验模型,采用阶梯升压方式,利用数字式局部放电检测仪采集信号,得出了不同加压持续时间下最大放电量、平均放电量和放电重复频率的变化特征以及二维图谱Hqmax(φ)、Hqn(φ)、Hn(φ)、放电幅值灰度图和放电能量灰度图的信息。
关键词:
干式空心电抗器,匝间绝缘,局部放电,特征参量,阶梯电压
DOI:10.15938/j.jhust.2018.03.013
中图分类号: TM406
文献标志码: B
文章编号: 1007-2683(2018)03-0072-07
Characteristics of PD for Dry-type Air-core Reactor
in Turn-to-turn Insulation under Step-voltage
YAO Yuan-hang1, WEI Xin-lao1, YANG Sheng-sheng2, GU Zhe-yi1, NIE Hong-yan1
(1.School of Electrical and Electronic Engineering, Harbin University of Science and Technology, Harbin 150080, China;2. Kunshan Special Transformer Manufacturing Co. Ltd, Kunshan 215312, China)
Abstract:Turn-to-turn insulation breakdown is the final expression form of turn-to-turn insulation fault for the dry-type air-core reactor, the partial discharge under over voltage is one of the main factors causing the turn-to-turn insulation damage. In order to study the rule of the partial discharge along with the development of the voltage for the dry-type air-core reactor turn-to-turn insulation, the test platform was constructed in the partial discharge shielding room. This paper references the manufacture process of 35kV dry-type air-core reactor turn-to-turn insulation, and make the turn-to-turn insulation partial discharge test model, then get the partial discharge signal with the digital partial discharge detector in the way of step-voltage. From the results, the variation characteristics of the maximum discharge, average discharge, discharge repetition frequency, and the two-dimensional phase resolved partial discharge pattern of Hqmax(φ), Hqn(φ), Hn(φ), discharge amplitude grayscale, discharge energy grayscale can be obtained under different step-voltage tests of step-up duration.
Keywords:dry-type air-core reactor; turn-to-turn insulation; partial discharge; characteristic parameter; step-voltage
0 引 言
干式空心电抗器对于改善电能质量、提高电力系统稳定性具有重要的作用,被广泛应用到电网中[1-2]。然而,在运行中也存在着不少问题。在分析导致干式空心电抗器绕组绝缘故障的原因中发现,匝间绝缘缺陷是造成电抗器匝间绝缘击穿的主要原因[3-4]。这些缺陷点在过电压的作用下会产生局部放电,使匝间绝缘性能逐渐劣化,从而导致匝间绝缘击穿,引起电抗器起火,给电力系统带来极大的安全隐患和经济损失[5-7]。为了减少由局部放电引起绝缘性能劣化的问题,对干式空心电抗器匝间绝缘局部放电特性进行研究具有重要意义。