那吉电厂913开关过电压保护器故障分析
2018-04-25陈健
陈健
摘 要:文章以那吉电厂为例,对其913开关过电压保护器中存在的故障分析,分析原因主要是氧化锌阀片通流量过大,引起电容变值,从而诱发了系统发生谐振,而过电压保护器中性点没有接地,使其工况恶化,出现三相短路,从而导致出现柜内过电压保护器发生爆炸。
关键词:电厂;开关;过电压保护器;故障
中图分类号:TM862 文献标志码:A 文章编号:2095-2945(2018)11-0113-02
Abstract: In this paper, taking Naji Power Plant as an example, the fault analysis of its 913 switching overvoltage protector is made. The main reason is that the passing flow of zinc oxide valve is too large, which causes the change of capacitance, which induces the resonance of the system. But the neutral point of the over-voltage protector is not grounded, which makes its working condition worsen and the three-phase short circuit appears, which results in the explosion of the over-voltage protector in the cabinet.
Keywords: power plant; switch; overvoltage protector; fault
1 故障概況
2011年2月10日下午14时16分,随着一声巨响,上位机显示10.5kV 913开关、400V 431开关同时跳闸,并发出“3#厂变保护动作”信号,屏幕显示400V厂用三段电源消失。值班人员赶往故障现场时发现913开关柜冒烟,柜内过电压保护器发生爆炸。
事后,经维护人员将过电压保护器拆除时,发现保护器三相高压接线端子出现灼伤脱落,A相和C相装置外壳被炸开,B相外壳也有一道8厘米的裂痕,A相阻容吸收装置的一个电容模块被炸飞。
在对#3厂用变保护装置检查时发现过流保护动作,A、B、C三相电流分别为8765A、8755A和8760A,从数据上可以判断913开关出线发生了三相短路。
2 故障分析
2.1 故障设备情况
故障设备为TCL明创(西安)有限公司生产的FGB型复合式过电压保护器,型号:FGB-10P,额定电压:10kV,工频放电电压为16kV。设备的系统接线图及保护器原理接线图如图1、图2。
2.2 10.5kV母线II段发生谐振过电压
在#3厂变保护动作前两秒,监控系统发“10.5kV母线II段消谐装置告警”信号,事后经查询录波装置,发现故障时波形如图3所示。