一种从供、用电两侧提高停车楼进、出口运行可靠性的供配电系统改造方案的探讨
2018-03-10刘畅姜雪晶金鑫沈健
刘畅+姜雪晶+金鑫+沈健


【摘 要】国内某大型国际枢纽机场停车楼进、出口的运行可靠性不仅关乎旅客能否顺利抵、离机场,还对停车楼的经营收益产生一定影响。论文对该枢纽机场停车楼进、出口现有的供配电系统存在的不足进行了分析,提出一种从供、用电两侧同时考虑的供配电系统改造方案,该方案相比于仅从电源侧进行改造,能够大幅提升停车楼进、出口通道的运行可靠性。
【Abstract】The operational reliability of the entrance and exit of a large domestic international hub airport is not only related to whether the passengers can arrive and leave the airport smoothly, but also has a certain impact on the operating revenue of the parking lot. The paper analyzes the shortage of the existing power supply and distribution system of the entrance and exit of the hub airport parking building, and puts forward a power supply and distribution system transformation scheme based on the consideration of the supply side and electricity side. Compared to the only transformation of the power supply side, the scheme can greatly improve the operational reliability of the entrance and exit passages of the parking building,
【关键词】供配电系统;停车楼;可靠性;改造
【Keywords】power supply and distribution system; parking building; reliability; transformation
【中图分类号】TM73 【文献标志码】A 【文章编号】1673-1069(2018)02-0191-03
1 引言
随着我国民航业的高速发展,每日有近30万旅客抵、离国内某大型国际枢纽机场。之前曾由于各种原因造成停车楼进、出口通道供电中断,例如:老鼠钻进配电箱汇流排引起短路从而导致上游馈线跳闸、单路供电电缆故障、出口生活用电故障导致上游线路越级跳闸等,都造成全部进口或者出口供电中断,恢复供电时间一般大于30min,甚至长达数小时,一定程度上影响了进、出口的运行效率,同时也给停车楼的经营收益造成一定损失。为提高停车楼进、出口的运行可靠性,降低因此类问题引发的不良影响,对停车楼进、出口供配电系统[1]的改造势在必行。
以往的改造方案主要是从电源侧着手,通过增加双电源互投设备[2]提高供电可靠性[3]。但互投设备以下仍为单路供电,当下游设备发生故障时,仍可能会导致供电中断,严重时影响全部进、出口运行,供电恢复时间依旧较长,无法从根本上解决因长时间供电中断对进、出口运行造成的影响。……