快速切除220kV变压器死区故障的继电保护技术实践研究
2018-01-03王洪涛
王洪涛
摘 要:在现阶段电力死区故障处理过程中,快速切除220kV变压器死区故障是电力控制的新模式,其可以在保证死区故障合理预防的同时,为后续电力系统稳定运行提供依据。文章以某侧断路器死区故障为例,阐述了快速切除220kV变压器死区故障所有故障点及故障因素,对220kV变压器在其故障切除中的应用进行了简单的分析。以期为快速切除220kV变压器死区故障继电保护技术的合理应用提供有效的借鉴。
关键词:220kV;变压器;死区故障;继电保护技术
中图分类号:TM772 文献标志码:A 文章编号:2095-2945(2018)33-0149-02
Abstract: In the current stage of power dead-time fault processing, rapid removal of 220kV transformer dead-zone fault is a new mode of power control, which can ensure the reasonable prevention of dead-time fault and provide the basis for the follow-up power system stable operation. Taking one side circuit breaker dead zone fault as an example, this paper expounds all fault points and fault factors of fast removing 220kV transformer dead zone fault, and simply analyzes the application of 220kV transformer in its fault removal, in order to quickly remove the dead zone fault of 220kV transformer relay protection technology and thus to provide an effective reference for the rational application.
Keywords: 220kV; transformer; dead-zone fault; relay protection technology
前言
220kV變压器的继电保护方案主要是在运行设备发生短路故障,将故障屏蔽在电网运行范围外的一种继电保护方法。220kV变压器继电保护模式的设计,虽然在一定程度上提升了短路故障处理效率,但是不可避免的在保护范围上出现了死区。这种情况下,短路故障问题就无法有效处理。因此,对快速切断220kV变压器死区故障继电保护方案进行适当探究具有至关重要的意义。
1 220kV变压器中压侧死区故障概述
如上图所示,2017年05月15日,某电网发生一起220kV变压器中压侧死区故障。整体事故发生的根本原因为在3号主变压器安装过程中,在其吊装变压器110kV侧断路器工作结束后,相关工作人员在断路器上方隔离开关操作位置,进行吊装钢丝绳的收集。而由于作业人员没有考虑钢丝绳弹性的变化,将钢丝绳从隔离开关位置向下滑落的过程中,最终降落到1号主变压器110kV侧断路器位置(图上所示短路位置),最终导致与断路器相连接的导线出现接地短路情况。……