APP下载

330 kV智能变电站二次系统联调方法探索

2017-10-09李江鹏宁永龙

电气自动化 2017年3期
关键词:变电站智能故障

李江鹏, 宁永龙

(吴忠供电公司,宁夏 吴忠 751100)

330 kV智能变电站二次系统联调方法探索

李江鹏, 宁永龙

(吴忠供电公司,宁夏 吴忠 751100)

介绍了某330 kV新建变电站的基本情况和二次系统联调方法,通过对SCD文件的配置和检查,对站内过程层、间隔层、站控层设备的单体测试和联合调试,总结了330 kV智能变电站联调的主要思路、项目和方法,为新建智能变电站联调测试提供参考。

智能变电站;IEC61850;SCD文件;组态;联调

Abstract: This paper contains basic information about a new 330kV substation and the joint debugging method for its secondary system. On the basis of SCD file configuration and inspection as well as unit test and joint debugging of its equipment on the process layer and spacer layer and its equipment on the station control layer, it summarizes main ideas, projects and methods for joint debugging of the 330kV intelligent substation, thus providing a reference for joint debugging of new intelligent substations in the future.

Keywords: intelligent substation; IEC61850; SCD file; configuration; joint debugging

0 引 言

随着智能电网建设的逐步推进,新建的变电站大多都采用了基于IEC61850规约的智能变电站。由于目前智能变电站正处于发展阶段,智能变电站二次设备可能存在一些问题。为了加快智能变电站的施工进度和提高智能变电站的运维质量,尽可能的在变电站投运前解决发现的问题,智能变电站的二次系统联调就显得尤为重要。

1 联调变电站基本情况

本次联调的变电站共有三个电压等级,分别为330 kV、110 kV和35 kV,其中330 kV部分采用3/2接线形式,110 kV部分采用双母双分段接线形式,35 kV部分采用单母分段接线形式。二次系统配置中,330 kV过程层未配置合并单元,110 kV过程层配置合并单元。表1所示是本次联调涉及的二次系统配置表。

2 变电站联调依据的标准和规范

目前,智能变电站联调的主要依据为IEC61850-9-1-2003《变电站通信网络和系统》和国家电网公司颁布的技术标准和规范,比如Q/GDW 383—2009 《智能变电站技术导则》、Q/GDW1809-2012《智能变电站继电保护检验规程》、Q/GDW1810-2012《智能变电站继电保护检验测试规范》、Q/GDW426-2010《智能变电站合并单元技术规……