APP下载

加压送风设计中余压阀的合理性设置探讨

2015-10-21何清衡

建筑工程技术与设计 2015年29期

何清衡

摘要:防烟楼梯间、消防电梯前室、合用前室作为火灾时建筑中重要的逃生通道,对保障人员安全起着至关重要的作用,为避免加压送风过程中加压空间室内超压现象的发生,工程中经常采用设置余压阀的做法,本文就加压部位超压产生的原因以及余压阀的合理性设置进行了初步的探讨,对余压阀计算面积公式进行了优化。

关键词 : 楼梯间;合用前室;加压送风;余压阀

The rationality of the residual pressure valve set in the pressurized design of air supply

He Qingheng1

(1. Guangzhou Building Equipment Installation Engineering Quality Monitoring Station, Guangzhou, 510410)

Abstract:Smoke-proof staircase, fire elevator former room, share former room as the important emergency exits for fire building plays an vital role in personnel safety. To avoid the overpressure phenomenon in the pressure space while doing the process of the pressurized air supply, people often set pressure valve in engineering practice. In this paper, the causes of overpressure phenomenon and the rationality of the pressure valve set has carried on the preliminary discussion. The pressure valve area calculation formula is optimized.

Keywords : Staircase; Share former room; Pressurized air supply; Pressure valve

0 引言

随着我国现代化城市建设的发展, 建筑业发展迅速, 各地高层建筑大量兴建,防烟楼梯间作为高层建筑中重要的火灾逃生通道,对保障人员安全起着至关重要的作用。国内外的有关资料表明, 高层建筑物中火灾造成的人员伤亡有80% 左右是由于燃烧产生的烟气使人窒息而死。因此, 在建筑物中对楼梯间、前室(合用前室)采用加压送风的方式防烟在国内外高层建筑设计中已被广泛接受与采用。为了防止火灾时安全疏散门无法打开的现象发生(有资料表明,当余压值在102Pa左右時,疏散门就难以打开),加压送风设计中应避免加压部位室内空间压力超压,经常采用的有余压阀泄压、采用变频技术调节送风机风量和采用风量旁通调节3 种方式调整竖井内压力大小, 其中采用余压阀较简单且有较高的可靠性。本文就余压阀的合理性设置进行了初步探讨,对余压阀计算面积公式进行了优化。。

1. 超压的危险性

我国国家标准GB50045-95《高层民用建筑设计防火规范》[1] (以下简称“《高规》”)中8.3.7规定:机械加压送风机的全压,除计算最不利环管道压头损失外,尚应有余压。……

登录APP查看全文