普洱换流站极Ⅱ做线路中点对地故障时双阀组跳闸的分析研究
2015-09-16周仁伟等
周仁伟等



摘 要: 针对2014年1月22日普洱换流站进行极Ⅱ线路中点的接地故障实验时发生的双阀组跳闸事件,详细分析了保护动作的情况,指出所提出的直流保护方法正确和有效;并根据保护的范围分析了可能发生故障的区域和原因,对故障区域内的设备进行测试,找出了发生故障的避雷器,表明直流线路故障保护控制协调策略相关分析的正确性,为以后类似问题的分析提供有益参考。
关键词: 直流输电; 避雷器; 行波保护; 差动保护
中图分类号: TN702?34 文献标识码: A 文章编号: 1004?373X(2015)18?0147?04
Abstract: Since the bivalve group trip event occurred in pole II circuit of Puer converter station when an experiment of the midpoint ground fault was executed on 22th January 2014, the situation of protection action is analyzed in detail. The correctness and validity of the DC protection method proposed in this paper are pointed out. The areas and reasons of faults which may occur are analyzed according to the protection region. The equipments in fault region were tested, and the fault arresters were found out. It proves that the correlation analysis of the control and coordination strategy to DC transmission line fault protection is correct and effective. This scheme provides a beneficial reference for analysis of the similar problems.
Keywords: DC transmission; arrester; traveling wave protection; differential protection
0 引 言
±800 kV普侨直流是南方电网第二个±800 kV,输电容量500万kW的特高压,大容量直流输电工程,工程包括普洱、侨乡两座换流站,以及普洱至侨乡全长1 413 km的输电线路。其中,普洱换流站位于云南省普洱市龙潭村,为普侨直流的整流站。直流输电系统常用的运行方式有双极运行方式、单极大地回线方式和单极金属回线方式,如果需要以单极方式运行较长时间时,往往会采用单极金属回线接线方式[1?3]。然而,由于直流线路沿线地区环境污染,外力破坏以及雷击等因素的影响,直流线路故障率逐年升高,成为直流输电最经常发生的故障。目前,世界上广泛采用行波保护作为高压直流线路保护的主保护。本文详细分析了普侨直流金属回线方式下线路中点接地实验中保护动作状况,根据保护控制策略,判断故障区域,并找出产生问题的设备[4?7]。
1 普侨直流背景
普洱换流站极Ⅱ单极双阀组金属回线运行的接线如图1所示,图中简单列出了一些电流电压的测点和一些一次设备;……