Abstract: water concrete is the concrete pouring surface or in a transparent protective agent do protective treatment of concrete surface as the outer surface, through the concrete own sense and elaborate design and construction of appearance quality to achieve the effect of beautiful cast-in-situ concrete engineering, new 500 kv substation project merit target key to achieving rinse concrete structure construction control meets the technical requirements. In this paper I presided over a national high quality project and the new 500 kv substation main construction technical requirements and measures are presented here, in the same field for reference.

Keywords: rinse concrete; Concrete; substation

中图分类号:TM411+.4文献标识码:A 文章编号:2095-2104(2012)

1.清水砼的技术要求

清水混凝土除满足普通混凝土的技术要求外, 还须满足以下技术要求。

1.1 表面质量要求

(1)颜色:混凝土颜色基本一致,距离墙面5m看不到明显色差。

(2)裂缝:表面无明显裂缝,不得出现宽度大于0.2mm 或长50mm以上的裂缝。

(3)气泡:混凝土表面的气泡要保持均匀、细小,表面气泡直径不大于3mm,深度不大于2mm,每m2表面的气泡面积小于150mm2。

(4)平整度:要求达到高级抹灰的质量验收标准,允许偏差不大于2mm。

(5)光洁度:脱模后表面平整光滑,色泽均匀,无油迹、锈斑、粉化物,无流淌和冲刷痕迹。

(6)观感缺陷:无漏浆、跑模和胀模造成的缺陷,无错台,无冷缝或夹杂物,无蜂窝、麻面、孔洞及露筋,无剔凿或涂刷修补处理痕迹。

1.2 装饰效果要求

(1)整栋建筑的明缝、禅缝要求表现出线条的规律和韵感,竖缝应垂直成线,平缝应形成首尾连接的水平环圈。线条要求平整、顺直、光滑、均匀,整体建筑中明缝、禅缝的交圈,允许偏差不大于5mm。……