广州白云国际会议中心2500座大厅空调设计
2012-04-10安天华
安天华
【摘要】本文介绍了广州白云国际会议2500座观众厅置换通风空调系统的设计计算过程,对观众厅的空调设计参数的选取、通风排烟系统设计、空调自动控制系统和消声措施也进行了介绍。
【关键词】观众厅;置换通风;空调设计;
中图分类号:S611文献标识码:A文章编号:
Design of Air Conditioning System for Shiji Hall's Auditorium in
Guangzhou International Conference Centre
An Tianhua
(1. Guangzhou Pearl River Foreign capital Construction Design instituteGuangzhou510060)
【Abstract】The design and calculate process of air conditioning system for the Shiji hall's auditorium in Guangzhou international conference centre are introduced in this article, the design variable's selection of the audience hall's air conditioning, ventilation and discharges fume system's design, automatic control system of the air conditioning system and noise elimination measure have been introduced emphatically.
【Keywords】auditorium; replacing ventilation; air conditioning design
引言
广州白云国际会议中心是广东省重点工程,是以会议为主体,配套展览、酒店等设施的大型综合性会议中心。工程由A、B、C、D、E栋单体组成。2500座大厅是D栋中最大的一个会议厅,共可容纳2500人,主席台可设180座,一层座位1172个,二层座位805个,三层650个,观众区高24m。适合举办各类大型政务和商务会议及国际国内高规格演出。
1设计参数
1.1室外设计参数
广州市位于夏热冬暖地区,室外设计参数如下:夏季干球温度33.5℃,湿球温度27.7℃,平均风速1.8m/s,主导风向西南向;冬季干球温度5℃,相对湿度70%,平均风速2.4m/s[1]。
1.2室内设计参数
表1 室内设计参数表[2]
Table 1 indoor designing parameter
温度(℃) 相对湿度(%) 新风量 允许噪声值
夏季 冬季 夏季 冬季 m3/h·人
25 20 ≤60 ≥30 30 NR25
1.3送风温差与垂直温度梯度
Δts=Δtf+Δtn(1)
式中Δts—送风温差,℃;Δtf—地面温升,℃;Δtn—脚踝到头部的温差,℃。
影响人体舒适性的是脚踝到头部的温差Δtn。按照ISO7730(2005)标准[3],对坐姿人员头部与脚踝处空气温差Δt1.1=t1.1-t0.1<3℃;按ASHRAE55(2004)标准[4],对站立者头与脚处空气温差Δt1.8=t1.8-t0.1<3℃;根据国家大剧院的设计经验,由于地面温升Δtf较难确定,而测得的Δtf/Δts在0.24~0.49之间。则本工程的的设计送风温差Δts定为4℃,基本能满足国际标准规定的头脚间的温差Δt1.1=t1.1-t0.1<3℃的要求。
1.4空调负荷
观众厅、主侧舞台整个大会堂位于建筑物内区,没有外围护结构,主要负荷为新风负荷,其次为人员负荷。本工程采用鸿业负荷计算软件对空调区域进行了逐项逐时负荷计算,各区域冷热负荷如表2:
表2 空调负荷表
Table 2 air conditioning load
区域 面积㎡ 计算冷负荷
kW 单位面积冷负荷W/㎡ 计……