热水采暖系统常见故障及处理措施分析
2012-03-23吴春利
吴春利
摘要:目前热水采暖广泛用于工业和民用建筑中,但是由于施工作业人员在热水采暖系统的施工、调整与运行管理方面的经验不足,系统在运行时可能会出现一些故障,影响正常供热。本文主要分析了热水采暖系统不热的原因,具体从设计、施工及运行管理三个方面对其进行了深入论述,并提出了一些相应的改进措施,可供施工人员参考。
關键词:设计; 施工; 运行管理; 散热器;
Abstract: At present, the hot water heating widely used in industrial and civil building, but because the construction work personnel in the hot water heating system construction, adjust and operation management experience, system in operation may appear some fault, affect the normal heating. This paper mainly analyzes the hot water heating system is not the cause of the heat, and the specific from design, construction and operation management of the three aspects of its further discussed, and puts forward some corresponding improvement measures for construction personnel reference.
Key Words: design; construction; operation management; radiator
中图分类号:S611 文献标识码:A 文章编号
前言
近年来热水采暖以其在技术和经济上的显著优越性得到广大用户的青睐。目前热水采暖广泛用于工业和民用建筑中。但是由于设计、施工作业人员在热水采暖系统的设计、施工、调整与运行管理方面的经验不足,系统在运行时可能会出现一些故障,影响正常供热。本文主要论述了热水采暖系统不热的常见原因及解决方法, 仅供同类工程参考。
一、设计方面分析
1、热媒设计参数定得过低。高层建筑物在以热水为媒介的热水采暖中, 由于锅炉承压能力所限, 锅炉输出的水( 约为 90℃ ) 不能直接送到供暖点的散热器, 只能通过换热设备。而换热设备的出水温度只有 70℃ 左右,设计人员把热媒定为 70℃ 或 55℃ , 这就明显地影响了传热效果。为了加大散热量, 势必得增加散热器的片数, 从实际运行情况来看, 散热面积的增加将进一步造成运行时热媒参数降得更低, 如此便形成恶性循环, 导致暖气散热量不够, 保证不了供暖室温要求。……