防跳回路的分析与改造

2012-03-23张金满戴延峰索鹏程

城市建设理论研究 2012年4期

张金满 戴延峰 索鹏程

摘要:针对存在于承钢第二变电站三条6kV进线的控制回路中两套防跳回路所带来的异常现象,本文着重从微机保护和断路器机构防跳回路的原理出发进行分析,比较了微机保护中的防跳与机构内防跳作用的差异,指出了目前常采用的取消寄生回路措施所存在的问题,提出了一种较为成熟的改进方案。

关键词:断路器;防跳;微机保护

Abstract: aiming at the existing YuChengGang second substation three 6 kV into line of control circuit two sets of defend jump circuit brings the abnormal phenomenon, this article emphatically from the microcomputer protection and circuit breaker institutions defend jump circuit principle is analyzed, and compared the microcomputer protection of the spring prevention and institution in the difference of the jump role, and points out that the current often used to cancel the parasitic loop measures of the existing problems, this paper puts forward a kind of more mature improvement plan.

Key words: breaker; Defend jump; Microcomputer protection

中圖分类号:TM561文献标识码:A 文章编号:

1 引 言

防跳是防止断路器跳跃的简称。所谓跳跃是指由于合闸回路的问题引起合闸触点粘连,造成长期发出合闸命令,当断路器合于故障跳开后,合闸命令又使其合上,保护动作使断路器再次跳开,因为一直有合闸命令,断路器又会再次合上,断路器如此“合-跳-合-跳”往复循环的现象。一旦发生断路器跳跃现象,会导致断路器损坏,严重的还会造成断路器爆炸,所以防跳功能是操作回路里一个相当重要的部分。目前,在微机保护的操作回路和大多数断路器机构中均设计有防跳回路,2套防跳回路的并存,使得合闸回路中难免会出现直流寄生回路,导致合闸后红绿灯同时亮,分闸后想再次合闸就合不上等异常现象。针对此现象,本文将分别从微机保护防跳原理和断路器机构防跳原理出发,找到此类问题的解决办法。

2 微机保护防跳与断路器机构防跳的原理

2.1 微机保护的防跳回路

图1是施耐德保护操作回路部分原理图,其防跳功能通过跳闸保持继电器KLT.A和防跳继电器KLT.V共同实现。……