浅谈热源与热网参数的匹配优化
2012-03-23周瑞昆王红卫彭增彬李伟腾
周瑞昆 王红卫 彭增彬 李伟腾
摘要:现有热水锅炉直供的采暖系统中,热网与锅炉参数大多不匹配,往往又未采取相应措施,因此造成循环水泵功耗大大增加,影响锅炉安全经济运行,甚至造成部分用户不热,降低供暖质量。本文根据不同实际情况,选择相应的优化匹配系统,达到既满足供暖要求,又保证锅炉安全经济运行的目的,同时降低水泵功耗,并节省投资。
关键词: 热水锅炉热网参数匹配优化旁通分流节能
Abstract: the existing hot water boiler straight for the system of heating, piping and boiler parameters don't match mostly, often and fails to take measures, this causes the circulating water pump power consumption increase greatly, affect the boiler safe and economic operation, even cause some users not hot, and reduce the heating quality. This paper according to different actual situation, choose corresponding optimization match system, meet heating request, and to ensure the safety of economic operation of the objective, at the same time, reduce the power consumption of the water pump, and to save investment.
Keywords: hot water boiler piping matching parameters optimization bypass tap the energy
中图分类号:TU833+.3 文献标识码:A文章编号:
1.引言
在热水锅炉直供的采暖系统中,不仅锅炉的热负荷必须满足热网的要求,而且其参数也应相匹配,这些要求应在设计中考虑。即使在设计时已经考虑了匹配问题,但是在实际运行中,受各种因素影响,热网有些参数偏离设计值较大,要满足热负荷要求,往往使流量增大,导致锅炉内部阻力增加,循环水泵功率增大,甚至造成部分用户不热,影响供暖质量。例如采用低温热水锅炉直供的普通采暖系统,锅炉与供暖系统热负荷相同,供、回水温度均为95℃/70℃,但实际运行中,热网系统供、回水温差大多在15℃-20℃之间,即使按照20℃计算,流量G将增加1.25倍,全部通过锅炉,则锅炉阻力H(与流速平方成正比)增加1.56倍,则用于克服锅炉阻力的水泵功率P=KρGH/(102η)(式中ρ:水的密度Kg/ m3、K:修正系数、G:水泵输出流量m3/s、H:水泵扬程m、η:水泵效率)需增至1.95倍。显然若锅炉按照设计值配置水泵,不可能满足供暖要求,造成供暖质量下降。若采用高温热水锅炉,而不采取任何措施,直接降至供暖系统参数运行,则矛盾更加突出。……