APP下载

浅谈我国南方丘陵地区中压配电网的防雷措施

2012-03-23蒙曰心

城市建设理论研究 2012年4期
关键词:配电网

蒙曰心

摘要:我国南方丘陵地区雷电现象频发,对该地配电网安全运行构成极大的危害。本文结合配电网实际运行中的雷害情况,全面分析了配电网的防护现状,提出了降低杆塔接地电阻、提高线路绝缘、特殊地段增设架空避雷线、安装线路避雷器、架设耦合地线等多种防雷措施,可供同行人员借鉴。

关键词:丘陵地区;配电网;防雷

Abstract: the hilly region in the south of lightning phenomena occur frequently, and the safe operation of the distribution network to pose a great harm. Combining with the actual operation of the power distribution network ray against situation, comprehensive analysis of the distribution network protection status, the lower tower grounding resistance, improve line insulation, special area overhead BiLeiXian, installation line add lightning arrester, set up the lightning protection and so on the many kinds of wire and the coupling, available for aboard the reference.

Key words: the hilly region; Distribution network; Lightning protection

中图分类号:F407.61文献标识码:A 文章编号:

丘陵地区是雷电活动频繁的地区,雷害事故仍经常发生,极大地影响了中压电网的供电可靠性,影响了电网的安全稳定运行。而作为我们国家的主要配电网络的中压电网(6~35kV)最易发生雷害事故。此类线路一般仅在两端进线侧1~2km架设架空地线,中间部分无避雷线、避雷器等,绝缘水平低,接地装置简单,地阻较高,且丘陵地区35 kV线路杆塔多位于山顶,雷电击杆率高,耐雷水平低。

1雷电对电力线路的危害

架空线路受到直接雷击或线路附近落雷时,导线上会因电磁感应而产生过电压,即大气过电压(外过电压)。这个电压往往高出线路相电压的2倍及以上,使线路绝缘遭受破坏而引起事故。当雷击线路时,巨大的雷电流在线路对地阻抗上产生很高的电位差,从而导致线路绝缘闪络。雷击不但危害线路本身的安全,而且雷电会沿导线迅速传到变电站,若站内防雷措施不良,则会造成站内设备严重损坏。根据统计08年我国南方的雷电日和落雷密度都高于往年,约60%的线路故障由于雷击造成,雷击跳闸率依然很高,且与往年一样,雷电活跃集中在每年的5、6、7三个月,以位居山地、丘陵为主。……

登录APP查看全文

猜你喜欢

配电网
配电网自动化的应用与发展趋势
关于城市10kV配电网自动化实施的探讨
关于配电网自动化继电保护的几点探讨
基于IEC61850的配电网数据传输保护机制
基于Zbus隐式高斯法的配电网潮流计算
一场配电网改造的攻坚战——信阳供电公司加快推进配电网改造略记
配电网不止一步的跨越
配电网非完全量测同期线损计算方法研究
基于LCC和改进BDE法的配电网开关优化配置
基于智能配电网关键技术的城市配电网规划