APP下载

气体灭火系统升级改造分析

2023-08-01张珊珊

现代信息科技 2023年11期

摘  要:文章通过对国家图书馆一期C栋建筑的深入研究,根据现行建筑防火和气体灭火设计规范,提出切实可行的改造方案,对保护区的气体灭火系统进行改造升级。对药量的计算,药剂的分装,瓶组的安装,管道的铺设、清扫、测试,以及灭火系统安装与调试进行全面阐述,展示改造优化的全过程,实现对防护区的有效保护。希望文章能为博物馆、图书馆类的气体灭火改造提供一些可供参考的内容。

关键词:气体灭火;七氟丙烷;管网系统

中图分类号:TP273+.5  文献标识码:A  文章编号:2096-4706(2023)11-0038-04

Analysis of Upgrading and Renovation of Gas Fire Extinguishing Systems

—Taking Building C of National Library of China Phase I as an Example

ZHANG Shanshan

(National Library of China, Beijing  100081, China)

Abstract: Through in-depth research on Building C of the National Library of China Phase I, and based on our current design standards for fire prevention and gas fire extinguishing, this paper proposes practical and feasible renovation plans to upgrade the gas fire extinguishing system in the protected area. Comprehensively elaborate on the calculation of drug dosage, drug dispensing, installation of bottle groups, pipeline laying, cleaning, testing, and installation and debugging of fire extinguishing systems, showcasing the entire process of transformation and optimization, and achieving effective protection of the protective zone. It is hoped that the paper can provide some reference content for gas fire extinguishing renovation in museums and libraries.

Keywords: gas fire extinguishing; heptafluoropropane; pipe network system

0  引  言

國家图书馆C栋一层网络机房气体灭火防护区此前是采用1301卤代烷气体灭火系统,它是1987年随主体建筑建成并投入使用的,距今已有35年。根据TSG 23—2021《气瓶安全技术规程》第3.7条,由于气体钢瓶已超过最高使用年限(无缝钢瓶不超过20年),已到报废处置年限。其次1301卤代烷灭火剂早已被国家禁止使用,需要更换。为保证网络机房防火灭火设施的可靠性和完整性,对保护区进行气体灭火系统改造。

1  项目概况

本项目分为配电室和网络机房两个独立区域。其原有保护区使用的是1301卤代烷气体灭火系统,依据GB 50016—2014《建筑设计防火规范》规定国家、省级或藏书量超过100万册的图书馆应设置气体自动灭火系统[1],现需更换为七氟丙烷气体灭火系统,施工的主要内容是对旧有的1301气灭管道及钢瓶进行拆除改造。委托专业设计单位进行系统设计,出具设计图纸,火灾自动报警系统延用原系统火灾探测器等并进行移位及新增,相应管线变更,其他不做变更。……

登录APP查看全文