INFIT实时优化控制系统在1000MW机组中的应用

2021-11-18钱其艺

家园·电力与科技 2021年10期

钱其艺

摘要:文章重点介绍了INFIT优化控制系统如何接管1000MW机组负荷控制中心和改变CCS控制方式,并详细说明了INFIT系统投运后机组各个重要参数是如何接受命令,并很好的配合控制机组运行的过程。文章中对比了两种控制方式的不同点,以及操作时有哪些注意事项。最后通过参数的历史趋势分析证明INFIT系统调节的优越性。

关键词:INFIT;协调控制方式;控制量;主汽温

Abstract:This paper focuses on how the infit optimal control system takes over the load control center of a 1000MW unit and changes the CCS control mode,It also explains in detail how the important parameters of the unit accept the command after the infit system is put into operation,And good coordination control unit operation process.In this paper,the differences between the two control methods are compared,as well as the precautions in operation. Finally,the advantage of infit system is proved by the analysis of the historical trend of the parameters.

Key words:infit;coordinated control mode;control quantity;main steam temperature

1、引言

电网出于安全考虑,会要求燃煤电厂尽量投入AGC运行,对电厂考核严格,电厂必须按照要求完成一次调频试验,试验数据合格才允许并网。1000MW 机组变成深度调峰机组受AGC指令控制,机组负荷大幅度上下波动,对机组主汽压力、主再热汽温、调门开度的稳定性有很大影响,设备设施的不安全因素增多,给设备运行的安全性产生重大威胁。某电厂1000MW 燃煤发电机组采用最新的实时优化控制系统 INFIT 接管机组本身 DCS 中的 CCS 协调控制系统、过热汽温、再热汽温控制模块,以此更好的保证机组参数稳定。

2、INFIT系统投切条件

在DCS“机组负荷控制中心”画面中点击“INFIT CCS”按钮,将弹出如图1画面。INFIT协调系统允许投入条件(条件全部满足):负荷指令在限速前后差值的绝对值<10MW;主汽压设定值在限速前后差值的绝对值<0.2MPa;压力的设定和实际值相差<0.4MPa;NFIT协调系统各项优化指令应正常跟踪DCS的当前指令[1]。INFIT系统自动切除条件(任一条件满足):非协调方式、发生Runback、水燃比控制在手动、机组在湿态方式、机组负荷低于480MW。当INFIT协调系统切除时,正常情况是无扰切换到DCS协调控制模式,若工况变化比较大满足相关条件时DCS协调控制模式将自动切换至TF运行方式,这也是出于机组安全运行考虑[2]。……