枕头坝水电站定子局部放电监测系统的创新应用
2021-11-17彭桂桦
彭桂桦



摘 要:定子绕组绝缘故障是大型发电机组的主要故障之一。发电机因定子绝缘故障引发的事故时有发生,不仅严重影响了发电企业的安全生产,还会产出昂贵的维修费用,造成巨大的经济损失。在运行状态下对发电机定子绕组的绝缘状况进行在线监测,可以有效了解发电机绝缘的状态,避免恶性事故的发生,为发电机组的安全运行提供保障。
关键词:绝缘;发电机;定子绕组
中图分类号:TM31文献标识码:A文章编号:1003-5168(2021)17-0043-03
Innovative Application of Partial Discharge Monitoring in
Stator of Zhentouba Hydropower Station
PENG Guihua
(National Energy Group Dadu River Pillow Dam Power Generation Co., Ltd.,Leshan Sichuan 614000)
Abstract: The stator winding insulation fault is one of the main faults of large-scale power electric generator. The generator accidents caused by stator insulation fault occur from time to time, which seriously affect the safety production of power generation enterprises and cause huge economic losses. The on-line monitoring of the insulation condition of the generator stator windings under operating conditions can effectively understand the insulation condition of the generator, avoid the occurrence of malignant accidents, and improve the reliability of the safe operation of the electric generator.
Keywords: insulation;generator;stator winding
1 發电机定子局部放电的基本情况
大型发电机定子线棒在生产过程中因制造工艺,在绝缘层间或绝缘层与股线之间可能存在气隙或杂质。发电机定子线棒的长期运行过程中,在电、热和机械力的联合作用下,会直接或间接出现绝缘劣化问题,使得绝缘层间产生新的气隙。在运行电压的作用下,气隙中的场强很容易达到击穿场强,造成绝缘体内部放电。内部放电会产生大量能量很大的带电粒子,这些高能带电粒子以很高的速度碰撞气隙壁,能够打断绝缘体的化学键,造成绝缘材料表面被侵蚀。局部放电产生的局部过热,也会造成高温聚合物裂解而使绝缘损坏。
在运行电压的作用下,通常气隙首先被击穿,形成局部放电。内部局放的电、热、化学和机械力的联合作用,会进一步扩大气隙,造成绝缘有效厚度减少,进一步降低击穿电压,最终导致绝缘击穿[1]。
局部放电产生的条件之一是电压,其次是充满空气的气隙或者气泡。……