Abstract Summary Construction fire water supply system is the focus of high-rise residential construction temporary water supply arrangement, how to set up the fire water supply system economically and effectively under the premise of satisfying the code has become a subject of exploration for construction technicians. Based on the engineering example, through the analysis and research of the construction fire water supply system, this paper summarizes the construction technology of the permanent-temporary combination of the construction fire water supply system.
Key words Fire Water Supply System; Permanent-temporary combination; Construction technology
引言
临时消防给水系统是建筑施工消防最重要的消防措施,《建设工程施工现场消防安全技术规范》GB50720—2011对施工现场临时消防给水系统做出了明确规定,其要点如下:
(1)临时用房建筑面积之和>1000㎡或在建工程单体体积>10000m?时,应设置临时室外消防给水系统。
(2)施工现场临时室外消防给水系统的给水管网宜布置成环状;给水干管的管径应依据施工现场临时消防用水量和干管内水流计算速度进行计算确定,且不应小于DN100;消火栓的间距不应大120m;消火栓的最大保护半径不应大于150m。
(3)建筑高度>24m或单体体积超过30000m?的在建工程,应设置临时室内消防给水系统。室内临时消防竖管设置位置应便于消防人员操作,其数量不应少于2根,当结构封顶时,应将消防竖管设置成环状;消防竖管的管径应根据在建工程临时消防用水量、竖管内水流计算速度进行计算确定,且不应小于DN100;各结构层均应设置室内消火栓接口及消防软管接口,其间距在高层建筑中≤30m。
(4)临时消防给水系统的压力应满足消防水枪充实水柱长度≥10m的要求; 给水压力不能满足规定时,应设置消火栓泵,其数量不应少于2台,且互为备用; 消火栓泵宜设置自动启动装置。……p>