环形通量对多模光纤插入损耗测试的影响分析
2020-08-13刘德强卢海萌冯仕琨解创创辛天禹
刘德强 卢海萌 冯仕琨 解创创 辛天禹



【摘要】介绍了多模光纤插入损耗测试的背景和意义;讨论了光源发射条件不同导致的多模光纤插入损耗测试结果不一致的问题;介绍了环形通量(Encircled Flux)及对多模光纤插入损耗测试的重要性;最后分别使用符合和不符合环形通量要求的光源对多模光纤插入损耗进行测试,并对测试结果进行了分析。
【关键词】多模光纤;插入损耗;光源发射条件;环形通量
【作者简介】刘德强:工程师,硕士研究生,从事光通信产品的测试与标准研究。
中图分类号:TN94 文獻标识码:A 文章编号:1673-0348(2020)012-127-03
Abstract: This paper introduces the background and significance of multimode fiber insertion loss test. The inconsistent test results of multimode fiber insertion loss caused by different emission conditions of light sources are discussed The encircled flux and the importance of testing the insertion loss of multimode fiber are introduced. Finally, the insertion loss of multimode fiber is tested by using light sources which meet and do not meet the requirements of encircled flux, and the test results are analyzed.
Keywords:multimode fiber; Insertion loss; Emission condition of light source; encircled flux
1. 引言
和单模光纤相比,多模光纤的芯径和数值孔径更大,可以从光源耦合更多的光功率。此外,相对于单模传输方案,多模传输方案可以采用低成本,低功耗的激光器。但是多模光纤由于色散大,不适合长距离传输。因此,多模光纤被广泛应用于数据中心短距离传输网络。
插入损耗是多模光纤的一个非常重要的参数,直接影响到链路的损耗。随着局域网的带宽越来越大,链路损耗预算也越来越紧,例如ISO/IEC/IEEE 8802-3规定,采用40G BASE-SR4/100G BASE-SR10方式传输数据时,100米长的OM3光纤链路可接受的链路损耗仅为1.9dB,150米长的OM4光纤链路可接受的链路损耗仅为1.5dB。在这样的严格限制下,对多模光纤插入损耗测试的准确性要求也越来越高。
2. 多模光纤插入损耗测试的问题
多模光纤插入损耗的测试在很大程度上取决于测试光源的发射条件。不同的光源会产生不同的发射条件。例如,一个LED光源将以“过满注入(Over fill)”的方式将光注入到光纤内,而一个激光器光源(如VCSEL)将以“欠注入(Under fill)”的方式将光注入到光纤内,如图1所示。……